24. PHYSICAL DIMENSIONS AND WEIGHT
Weight 425g / 0.94lb CD5.241
450g / 0.99lb CD5.241-S1
DIN-Rail Use 35mm DIN-rails according to EN 60715 or EN 50022 with a height of 7.5 or 15mm.
The DIN-rail height must be added to the depth (102mm) to calculate the total required
installation depth.
Electronic files with mechanical data can be downloaded at www.pulspower.com
Fig. 24-1
CD5.241
Front view
Fig. 24-2
CD5.241
Side view
Fig. 24-3
CD5.241-S1
Front view
Fig. 24-4
CD5.241-S1
Side view
25. INSTALLATION AND OPERATION INSTRUCTIONS
Mounting:
Output terminal must be located on top and input terminal on the bottom. For other orientations see chapter 27.13.
An appropriate electrical and fire end-product enclosure should be considered in the end use application.
Cooling:
Convection cooled, no forced cooling required. Do not cover ventilation grill (e.g. cable conduits) by more than 30%!
Installation clearances:
40mm on top, 20mm on the bottom, 5mm on the left and right side are recommended when loaded permanently
with full power. In case the adjacent device is a heat source, 15mm clearance are recommended.
Risk of electrical shock, fire, personal injury or death!
Turn power off before working on the DC/DC converter. Protect against inadvertent re-powering.
Make sure the wiring is correct by following all local and national codes.
Do not open, modify or repair the unit.
Use caution to prevent any foreign objects from entering into the housing.
Do not use in wet locations or in areas where moisture or condensation can be expected.
Supplying source, supplying network:
The inductance and resistance of the supplying network shall be below in Fig. 27-9 in chapter 27.10 to avoid resonant
effects on the input terminals. Please also check chapter 27.10.
Service parts:
The unit does not contain any service parts. The tripping of an internal fuse is caused by an internal fault. If damage
or malfunctioning should occur during operation, immediately turn power off and send unit to the factory for
inspection!