19. SAFETY
Input / output separation SELV IEC/EN 60950-1
PELV EN 60204-1, EN 50178, IEC 60364-4-41
Double or reinforced insulation,
Max. allowed voltage between any input pin and ground: 60Vdc or 42.4Vac
Class of protection II PE (Protective Earth) connection not required
Isolation resistance > 5MOhm Input to output, 500Vdc
Chassis Ground resistance < 0.1Ohm Between housing and Chassis Ground terminal
Touch current (leakage current) The leakage current which is produced by the DC/DC converter itself depends on
the input voltage ripple and need to be investigated in the final application.
For a smooth DC input voltage, the produced leakage current is less than 100µA.
20. DIELECTRIC STRENGTH
The output voltage is floating and has no ohmic connection to ground.
To fulfill the PELV requirements according to EN60204-1 § 6.4.1, it is recommend that either the + pole, the – pole or
any other part of the output circuit shall be connected to the protective earth system. This helps to avoid situations in
which a load starts unexpectedly or can not be switched off any more when an unnoticed earth faults occur.
CD5.241:
Fig. 20-1 Dielectric strength
A B C
Type test 60s 1500Vac 1500Vac 500Vac
Factory test 5s 1500Vac 1500Vac 500Vac
Field test 5s 1000Vac 1000Vac 500Vac
A
C
B
+
Input
Chassis
ground
Output
-
+
-
Type tests and factory tests:
Conducted by the manufacturer. Do not repeat test in field!
Rules for field test:
Use appropriate test equipment which applies the voltage
with a slow ramp! Connect all input poles together as well
as all output poles.
CD5.241-S1:
Fig. 20-2 Dielectric strength
A B C D
Type test 60s 1500Vac 1000Vac 500Vac 500Vac
Factory test 5s 1500Vac 1000Vac 500Vac 500Vac
Field test 5s 1000Vac 1000Vac 500Vac 500Vac
A
D
C
B
B
+
Input Signals
Chassis
ground
Output
-
+
-
Type tests and factory tests:
Conducted by the manufacturer. Do not repeat test in field!
Rules for field test:
Use appropriate test equipment which applies the voltage
with a slow ramp! Connect all input poles together as well
as all output poles.