24.12. MOUNTING ORIENTATIONS
Mounting orientations other than input terminals on the bottom and output on the top require a reduction in
continuous output power or a limitation in the max. allowed ambient temperature. The amount of reduction
influences the lifetime expectancy of the DC/DC converter. Therefore, two different derating curves for continuous
operation can be found below:
Curve A1 Recommended output current.
Curve A2 Max allowed output current (results in approximately half the lifetime expectancy of A1).
Fig. 24-6
Mounting
Orientation A
(Standard
orientation)
DC/DC
Converter
OUTPUT
INPUT
Output Current
0
10 20 30
40
60°
C
2
3
5
6A
50
A
1
Ambient Temperature
4
1
Fig. 24-7
Mounting
Orientation B
(Upside down)
DC/DC
Converter
OUTPUT
INPUT
Output Current
0
10 20 30
40
60°
C
2
3
5
6A
50
Ambient Temperature
4
1
A
2
A
1
Fig. 24-8
Mounting
Orientation C
(Table-top
mounting)
Output Current
0
10 20 30
40
60°
C
2
3
5
6A
50
Ambient Temperature
4
1
A
1
A
2
Fig. 24-9
Mounting
Orientation D
(Horizontal cw)
DC/DC
Converter
OUTPUT
INPUT
Output Current
0
10 20 30
40
60°
C
2
3
5
6A
50
Ambient Temperature
4
1
A
1
A
2
Fig. 24-10
Mounting
Orientation E
(Horizontal ccw)
DC/DC
Converter
OUTPUT
INPUT
Output Current
0
10 20 30
40
60°
C
2
3
5
6A
50
Ambient Temperature
4
1
A
1
A
2
22/22