Datasheet
CD5.241-S1
CD-Series 
DC/DC Converter 24V, 5A 
12. DC-OK RELAY CONTACT 
This feature is only available on the model CD5.241-S1 and monitors the output voltage, which is produced by the 
DC/DC converter itself. It is independent of a back-fed voltage from a unit which is connected in parallel to the DC/DC 
converter output. It is a “Normally Open” contact. 
Contact closes  As soon as the output voltage reaches the adjusted output voltage. 
Contact opens  As soon as the output voltage dips more than 10% below the adjusted output voltage. 
Short dips will be extended to a signal length of 250ms. Dips shorter than 1ms will be ignored. 
Contact re-closes  As soon as the output voltage exceeds 90% of the adjusted voltage. 
Contact ratings  max  60Vdc 0.3A, 30Vdc 1A, 30Vac 0.5A, resistive load 
  min  1mA at 5Vdc (minimum permissible load) 
Isolation voltage  See dielectric strength table in section 18. 
Note: 
The DC-ok feature requires that the output voltage reaches the nominal (=adjusted) level after turn-on in order to 
function according to specification. If this level cannot be achieved, the overload lamp will be on and the DC-ok 
contact will be open. The overload signal will only shut off as soon as the adjusted voltage is reached. This is an 
important condition to consider particularly, if the load is a battery, the DC/DC converter is used in parallel or the 
DC/DC converter is used for N+1 redundant systems. 
  Fig. 12-1 DC-ok relay contact behavior   
250ms
90%
V
ADJ
<
1ms
10%
open
V
OUT
=
 V
ADJ
openclosed closed
>
1ms
13. INPUT-LOW RELAY CONTACT 
This feature monitors the input voltage of the DC/DC converter. It is a “Normally Closed” contact. It can be used to get 
an alarm signal when the supplying battery becomes flat (under-voltage logout) 
Contact is closed  When the input voltage falls below 19.5Vdc (typ.) 
Contact opens  As soon as the input voltage reaches 20.5 Vdc (typ.) 
Contact ratings  max  60Vdc 0.3A, 30Vdc 1A, 30Vac 0.5A, resistive load 
  min  1mA at 5Vdc (minimum permissible load) 
Isolation voltage  See dielectric strength table in section 18. 
Oct 2009 / Rev. 1.3 DS-CD5.241-S1-EN 
All parameters are specified at 24V, 5A, 24Vdc input voltage, 25°C ambient and after a 5 minutes run-in time unless otherwise noted. 