Datasheet
CD5.241-S1
CD-Series
DC/DC Converter 24V, 5A
10. TERMINALS AND WIRING
Input Output
DC-OK and Input-low
Signal
Type
spring-clamp terminals spring-clamp terminals Plug-connector, screw type
Solid wire 0.5-6mm
2
0.5-6mm
2
0.2-1.5mm
2
Stranded wire 0.5-4mm
2
0.5-4mm
2
0.2-1.5mm
2
American Wire Gauge 20-10 AWG 20-10 AWG 22-14 AWG
Wire stripping length 10mm / 0.4inch 10mm / 0.4inch 6mm / 0.25inch
Screwdriver not applicable not applicable 3.5mm slotted or
Pozidrive No 2
Recommended tightening torque not applicable not applicable 0.4Nm, 3.5lb.in
Instructions:
a) The external circuitry of all terminals (including signalling contacts) must meet the safety requirements stipulated by
IEC/EN/UL 60950-1: SELV.
b) Use appropriate copper cables that are designed for an operating temperature of:
60°C for ambient up to 45°C and
75°C for ambient up to 60°C minimum.
c) Follow national installation codes and installation regulations!
d) Ensure that all strands of a stranded wire enter the terminal connection!
e) Up to two stranded wires with the same cross section are permitted in one connection point.
f) Do not load the terminals with more than 25A! See section 24.9
g) Screws of unused terminal compartments should be securely tightened.
h) Ferrules are allowed, but not required
11. RELIABILITY
Input 24Vdc
Lifetime expectancy
*) 180 000h at 24V, 2.5A and 40°C
60 000h at 24V, 5A and 40°C
33 000h at 24V, 6A and 40°C
169 000h at 24V, 5A and 25°C
MTBF
**) SN 29500, IEC 61709 1 048 000h at 24V, 5A and 40°C
1 719 000h at 24V, 5A and 25°C
MTBF
**) MIL HDBK 217F 602 000h at 24V, 5A and 40°C; Ground Benign GB40
807 000h at 24V, 5A and 25°C; Ground Benign GB25
*) The Lifetime expectancy shown in the table indicates the minimum operating hours (service life) and is determined by the lifetime
expectancy of the built-in electrolytic capacitors. Lifetime expectancy is specified in operational hours and is calculated according to the
capacitor’s manufacturer specification. The prediction model allows only a calculation of up to 15 years from date of shipment.
**) MTBF stands for Mean Time Between Failure, which is calculated according to statistical device failures, and indicates reliability of a
device. It is the statistical representation of the likelihood of a unit to fail and does not necessarily represent the life of a product.
The MTBF figure is a statistical representation of the likelihood of a device to fail. A MTBF figure of e.g. 1 000 000h means that
statistically one unit will fail every 100 hours if 10 000 units are installed in the field. However, it can not be determined if the failed unit
has been running for 50 000h or only for 100h.
Oct 2009 / Rev. 1.3 DS-CD5.241-S1-EN
All parameters are specified at 24V, 5A, 24Vdc input voltage, 25°C ambient and after a 5 minutes run-in time unless otherwise noted.
www.pulspower.com Phone +49 89 9278 0 Germany
10/22