Datasheet
CD5.121
CD-Series 
DC/DC Converter 12V, 8A 
5.  OUTPUT 
Output voltage  nom.  12V   
Adjustment range  min.  12-15V  guaranteed 
  max.  16.1V  at clockwise end position of potentiometer 
Factory setting    12.0V   ±0.2%, at full load, cold unit 
Line regulation  max.  25mV  Input voltage variations between 18 to 32.4Vdc 
Load regulation  max.  120mV  static value, 0A Æ 8A 
Ripple and noise voltage  max.  75mVpp  20Hz to 20MHz, 50Ohm 
Output current  nom.  9.6A  at 12V, ambient < 45°C, see Fig. 5-1 
  nom.  8A  at 12V, ambient < 60°C, see Fig. 5-1 
  nom.  7.7A  at 15V, ambient < 45°C, see Fig. 5-1
  nom.  6.4A  at 15V, ambient < 60°C, see Fig. 5-1
Output power  nom.  115W  for ambient temperatures < 45°C 
  nom.  96W  for ambient temperatures < 60°C 
Short-circuit current  min.  14A  continuous current, short circuit impedance 150mOhm 
 max. 18A continuous current, short circuit impedance 150mOhm 
Output capacitance  typ.  6 500μF   
Fig. 5-1 Output voltage vs. output current at 
24Vdc input voltage, typ. 
Fig. 5-2 Current limitation vs. input voltage, 
(11.5V constant voltage load), typ. 
Output Voltage
0
068
3
6
9
18V
12
15
18
A
16102 4 12 14
Adjustment
Range
Output Current
Output Current
9.8
15 21 27
10.0
10.2
11A
10.6
10.8
33Vd
c
302418
10.4
Input Voltage
Peak current capability (up to several milliseconds) 
The DC/DC converter can deliver a peak current, which is higher than the specified short term current. This helps to 
start current demanding loads or to safely operate subsequent circuit breakers. 
The extra current is supplied by the output capacitors inside the DC/DC converter. During this event, the capacitors will 
be discharged and causes a voltage dip on the output. Detailed curves can be found in chapter 22.1. 
Peak current voltage dips  typ.  from 12V to 8.3V  at 16A for 50ms, resistive load 
  typ.  from 12V to 6.2V  at 40A for 2ms, resistive load 
  typ.  from 12V to 4.3V  at 40A for 5ms, resistive load 
Oct 2009 / Rev. 1.3 DS-CD5.121-EN 
All parameters are specified at 12V, 8A, 24Vdc input voltage, 25°C ambient and after a 5 minutes run-in time unless otherwise noted. 
www.pulspower.com Phone +49 89 9278 0 Germany 