Datasheet

CT5.241
C-Series
24V, 5A, TWO-PHASE INPUT
7. HOLD-UP TIME
AC 400V AC 480V
Hold-up Time typ. 27ms 48ms at 24V, 5A, see Fig. 7-1
typ. 51ms 91ms at 24V, 2.5A, see Fig. 7-1
Fig. 7-1 Hold-up time vs. input voltage Fig. 7-2 Shut-down behavior, definitions
0
20
40
60
80ms
320 360 400 440 480Vac
Input Voltage
Hold-up Time at 24Vdc
2
.
5
A
,
t
y
p
.
5A
,
t
y
p
.
5
A
,
m
i
n
.
2
.
5
A
,
m
i
n
.
- 5%
Hold-up Time
Zero Transition
Output
Voltage
Input
Voltage
Jan. 2010 / Rev. 1.1 DS-CT5.241-EN
All parameters are specified at 24V, 5A, 400Vac, 25°C ambient and after a 5 minutes run-in time unless otherwise noted.
www.pulspower.com Phone +49 89 9278 0 Germany
7/21