Data Sheet
Table Of Contents
- 1. Intended Use
- 2. Installation Instructions
- 3. AC-Input
- 4. DC-Input
- 5. Input Inrush Current
- 6. Output
- 7. Hold-up Time
- 8. Efficiency and Power Losses
- 9. Functional Diagram
- 10. Front Side and User Elements
- 11. Connection Terminals
- 12. Lifetime Expectancy
- 13. MTBF
- 14. EMC
- 15. Environment
- 16. Safety and Protection Features
- 17. Dielectric Strength
- 18. Approved, Fulfilled or Tested Standards
- 19. Regulatory Product Compliance
- 20. Physical Dimensions and Weight
- 21. Accessories
- 21.1. ZM1.WALL - Wall/Panel Mount Bracket
- 21.2. ZM12.SIDE - Side Mount Bracket
- 21.3. YRM2.DIODE - Redundancy Modules
- 21.4. YR20.246 - Redundancy Module
- 22. Application Notes
- 22.1. Peak Current Capability
- 22.2. Charging of Batteries
- 22.3. Series Operation
- 22.4. Parallel Use to Increase Output Power
- 22.5. Parallel Use for Redundancy
- 22.6. Use in a Tightly Sealed Enclosure
- 22.7. Mounting Orientations
CT5.241
CT-Series
3-PHASE, 24V, 5A, 120W
Aug. 2021 / Rev. 2.1 DS-CT5.241-EN All values are typical figures specified at 400Vac, 50Hz input voltage, 24V, 5A output load,
25°C ambient and after a 5 minutes run-in time unless otherwise noted.
www.pulspower.com Phone +49 89 9278 0 Germany
4/28
The device is designed, tested and approved for branch circuits up to 32A (IEC) and 30A (UL) without additional
protection device. If an external fuse is utilized, do not use circuit breakers smaller than 6A B- or 3A C-Characteristic to
avoid a nuisance tripping of the circuit breaker.
The maximum surrounding air temperature is +70°C (+158°F). The operational temperature is the same as the ambient
or surrounding air temperature and is defined 2cm below the device.
The device is designed to operate in areas between 5% and 95% relative humidity.
Installation Instructions for Hazardous Location Areas
The device is suitable for use in Class I Division 2 Groups A, B, C, D locations.
WARNING EXPLOSION HAZARDS!
Substitution of components may impair suitability for this environment.
Do not disconnect the device or operate the voltage adjustment unless power has been switched off or the area is
known to be non-hazardous.