Data Sheet

CT5.241
CT-Series
3-PHASE, 24V, 5A, 120W
Aug. 2021 / Rev. 2.1 DS-CT5.241-EN All values are typical figures specified at 400Vac, 50Hz input voltage, 24V, 5A output load,
25°C ambient and after a 5 minutes run-in time unless otherwise noted.
www.pulspower.com Phone +49 89 9278 0 Germany
15/28
16. S
AFETY AND
P
ROTECTION
F
EATURES
Isolation resistance
Min. 500MOhm
At delivered condition between input and output,
measured with 500Vdc
Min. 500MOhm
At delivered condition between input and PE,
measured with 500Vdc
Min. 500MOhm
At delivered condition between output and PE,
measured with 500Vdc
Min. 500MOhm
At delivered condition between output and DC-OK
contacts, measured with 500Vdc
PE resistance
Max. 0.1Ohm
Resistance between PE terminal and the housing in
the area of the DIN rail mounting bracket.
Output over
-voltage protection Typ. 30.5Vdc
Max. 32Vdc
In case of an internal defect, a redundant circuit limits the maximum
output voltage. The output shuts down and automatically attempts to
restart.
Class of protection
I According to IEC 61140
A PE (Protective Earth) connection is required
Degree of protection
IP 20 According to EN/IEC 60529
Ove
r-temperature protection Included
Output shuts down with automatic restart.
Temperature sensors are installed on critical
components inside the unit and turn the unit off in
safety critical situations, which can happen e.g.
when ambient temperature is too high, ventilation
is obstructed or the derating requirements are not
followed. There is no correlation between the
operating temperature and turn-off temperature
since this is dependent on input voltage, load and
installation methods.
Input transien
t protection
MOV (Metal
Oxide Varistor)
For protection values see chapter 14 (EMC).
Internal input fuse
Included
Not user replaceable slow-blow high-braking
capacity fuse
Touch current
(leakage current) Typ. 0.14mA At 400Vac, 50Hz, TN-,TT-mains
Typ. 0.19mA At 480Vac, 60Hz, TN-,TT-mains
Max. 0.18mA At 440Vac, 60Hz, TN-,TT-mains
Max. 0.25mA At 528Vac, 50Hz, TN-,TT-mains