CT5.241 3-PHASE, 24V, 5A, 120W CT-Series POWER SUPPLY AC 380-480V Wide-range Input Input Fuses Already Included Requires only Two Legs of a 3-Phase System Width only 40mm Efficiency up to 90.
CT5.241 3-PHASE, 24V, 5A, 120W CT-Series INDEX Page 1. 2. 3. 4. 5. 6. 7. 8. 9. 10. 11. 12. 13. 14. 15. 16. 17. Intended Use .......................................................3 Installation Instructions ......................................3 AC-Input...............................................................5 DC-Input...............................................................6 Input Inrush Current ...........................................6 Output ...........................................
CT5.241 3-PHASE, 24V, 5A, 120W CT-Series 1. INTENDED USE This device is designed for installation in an enclosure and is intended for commercial use, such as in industrial control, process control, monitoring and measurement equipment or the like. Do not use this device in equipment, where malfunctioning may cause severe personal injury or threaten human life without additional appropriate safety devices, that are suited for the end-application.
CT5.241 3-PHASE, 24V, 5A, 120W CT-Series The device is designed, tested and approved for branch circuits up to 32A (IEC) and 30A (UL) without additional protection device. If an external fuse is utilized, do not use circuit breakers smaller than 6A B- or 3A C-Characteristic to avoid a nuisance tripping of the circuit breaker. The maximum surrounding air temperature is +70°C (+158°F). The operational temperature is the same as the ambient or surrounding air temperature and is defined 2cm below the device.
CT5.241 3-PHASE, 24V, 5A, 120W CT-Series 3. AC-INPUT The device is suitable to be supplied from TN-, TT- and IT mains networks with AC voltage. Grounding of one phase is allowed except for UL508 applications. Nom. External input protection AC 380-480V 323-576Va Continuous operation 576-700Vac For maximal 1s (occasional) Max. 500Vac Continuous operation, according to IEC 62477-1 Nom. 50–60Hz ±6% Typ. 270Vac Load independent, steady-state value, see Fig. 3-1 Typ. 185Vac At no load Typ. 215Vac At 24V, 2.
CT5.241 3-PHASE, 24V, 5A, 120W CT-Series 4. DC-INPUT Do not use the power supply with DC-input voltages. 5. INPUT INRUSH CURRENT An active inrush limitation circuit limits the input inrush current after turn-on of the input voltage and after short input voltage interruptions. The charging current into EMI suppression capacitors is disregarded in the first microseconds after switch-on. Inrush current Max. Typ. Max. Inrush energy AC 400V 10Apeak 4Apeak 0.5A2s AC 480V 10Apeak 4Apeak 0.
CT5.241 3-PHASE, 24V, 5A, 120W CT-Series 6. OUTPUT The output provides a SELV/PELV rated voltage, which is galvanically isolated from the input voltage. The device is designed to supply any kind of loads, including unlimited capacitive and inductive loads. The output is electronically protected against overload, no-load and short-circuits. In case of a protection event, audible noise may occur. Output voltage Adjustment range Nom. 24V 24-28V 30V Max. Typ.
CT5.241 3-PHASE, 24V, 5A, 120W CT-Series 7. HOLD-UP TIME Hold-up Time AC 400V 40ms 82ms 33ms 67ms Typ. Typ. Min Min. Fig. 7-1 Hold-up time vs. input voltage Hold-up Time at 24Vdc 100ms 75 A A... Typ. at 2.5A B... Min. at 2.5A C... Typ. at 5A D... Min. at 5A AC 480V 60ms 124ms 49ms 101ms At 24V, 5A, see Fig. 7-1 At 24V, 2.5A, see Fig. 7-1 At 24V, 5A, see Fig. 7-1 At 24V, 2.5A, see Fig. 7-1 Fig.
CT5.241 3-PHASE, 24V, 5A, 120W CT-Series 8. EFFICIENCY AND POWER LOSSES Efficiency Average efficiency *) Typ. Typ. AC 400V 90.4% 88.8% AC 480V 90.0% 87.9% Power losses Typ. Typ. Typ. Typ. 1.5W 7.5W 12.7W 15.3W 1.6W 7.7W 13.3W 15.8W At 24V, 5A 25% at 1.25A, 25% at 2.5A, 25% at 3.75A. 25% at 5A At 0A At 24V, 2.
CT5.241 3-PHASE, 24V, 5A, 120W CT-Series 9. FUNCTIONAL DIAGRAM Fig. 9-1 Functional diagram L1 L2 Input Fuses PFC Inductor Input Filter Inrush Limiter Input Rectifier Temperature Shutdown Power Converter Output Filter Transient Filter Output Power Manager Output OverVoltage Protection Output Voltage Regulator + + VOUT DC-ok LED 10. FRONT SIDE AND USER ELEMENTS Fig.
CT5.241 3-PHASE, 24V, 5A, 120W CT-Series 11. CONNECTION TERMINALS The terminals are IP20 Finger safe constructed and suitable for field- and factory wiring. Input Screw termination Max. 6mm2 Max. 4mm2 AWG 20-10 2.8mm 1Nm, 9lb-in 7mm / 0.28inch 3.5mm slotted or Phillips No 1 Type Solid wire Stranded wire American Wire Gauge Max. wire diameter (including ferrules) Recommended tightening torque Wire stripping length Screwdriver Output Screw termination Max. 6mm2 Max. 4mm2 AWG 20-10 2.
CT5.241 3-PHASE, 24V, 5A, 120W CT-Series 12. LIFETIME EXPECTANCY The Lifetime expectancy shown in the table indicates the minimum operating hours (service life) and is determined by the lifetime expectancy of the built-in electrolytic capacitors. Lifetime expectancy is specified in operational hours and is calculated according to the capacitor’s manufacturer specification. The manufacturer of the electrolytic capacitors only guarantees a maximum life of up to 15 years (131 400h).
CT5.241 3-PHASE, 24V, 5A, 120W CT-Series 14. EMC The EMC behavior of the device is designed for applications in industrial environment as well as in residential, commercial and light industry environments. The output is allowed to be grounded or floating. The device is investigated according to the generic standards EN 61000-6-1, EN 61000-6-2, EN 61000-6-3 and EN 610006-4.
CT5.241 3-PHASE, 24V, 5A, 120W CT-Series 15. ENVIRONMENT The operational temperature is the ambient or surrounding temperature and is defined as the air temperature 2cm below the device. -40°C to +85°C (-40°F to 185°F) For storage and transportation 1.6W/°C Between +45°C and +60°C (113°F to 140°F) 3W/°C Between +60°C and +70°C (140°F to 158°F) 7.5W/1000m or 5°C/1000m For altitudes >2000m (6560ft), see Fig. 15-2 For atmospheric pressures <80kPa, see Fig. 15-2 4.
CT5.241 3-PHASE, 24V, 5A, 120W CT-Series 16. SAFETY AND PROTECTION FEATURES Isolation resistance At delivered condition between input and output, measured with 500Vdc At delivered condition between input and PE, measured with 500Vdc At delivered condition between output and PE, measured with 500Vdc At delivered condition between output and DC-OK contacts, measured with 500Vdc Resistance between PE terminal and the housing in the area of the DIN rail mounting bracket. Min. 500MOhm Min. 500MOhm Min.
CT5.241 3-PHASE, 24V, 5A, 120W CT-Series 17. DIELECTRIC STRENGTH The output voltage is floating and has no ohmic connection to the ground. The output is insulated to the input by a double or reinforced insulation. Type and routine tests are conducted by the manufacturer. Field tests may be conducted in the field using the appropriate test equipment which applies the voltage with a slow ramp (2s up and 2s down). Connect all inputterminals together as well as all output poles before conducting the test.
CT5.241 3-PHASE, 24V, 5A, 120W CT-Series 18.
CT5.241 3-PHASE, 24V, 5A, 120W CT-Series 19.
CT5.241 3-PHASE, 24V, 5A, 120W CT-Series 20. PHYSICAL DIMENSIONS AND WEIGHT Width Height Depth Weight DIN rail Housing material Installation clearances Penetration protection 40mm 1.57’’ 124mm 4.88’’ 117mm 4.61’’ The DIN rail depth must be added to the unit depth to calculate the total required installation depth. 500g / 1.1lb Use 35mm DIN rails according to EN 60715 or EN 50022 with a height of 7.5 or 15mm. Body: Aluminium alloy Cover: Zinc-plated steel See chapter 2 Small parts like screws, nuts, etc.
CT5.241 3-PHASE, 24V, 5A, 120W CT-Series 21. ACCESSORIES 21.1. ZM1.WALL - WALL/PANEL MOUNT BRACKET These brackets are used to mount the device on a flat surface or panel without utilizing a DIN rail. The two aluminum brackets and the black plastic slider of the unit have to be detached, so that the steel brackets can be mounted in the holes of the aluminum brackets. The order number ZM1.WALL contains two brackets needed for one device. Fig. 21-1 ZM1.Wall Fig. 21-2 Hole pattern Fig.
CT5.241 3-PHASE, 24V, 5A, 120W CT-Series 21.2. ZM12.SIDE - SIDE MOUNT BRACKET This ZM12.SIDE bracket is used to mount the device sideways with or without utilizing a DIN rail to save installation depth. The two aluminum brackets and the black plastic slider of the unit have to be detached, so that the ZM12.SIDE steel bracket can be mounted. For sideway DIN rail mounting, the removed aluminum brackets and the black plastic slider need to be mounted on the ZM12.SIDE steel bracket. Fig.
CT5.241 3-PHASE, 24V, 5A, 120W CT-Series 21.3. YRM2.DIODE - REDUNDANCY MODULES The YRM2.DIODE is a dual redundancy module, which can be used to build 1+1 or N+1 redundant systems. The device is equipped with two input channels each 10A nominal, which are individually decoupled by utilizing diode technology. The output can be loaded with nominal 20A. The device does not require an additional auxiliary voltage and is self-powered even in case of a short circuit across the output.
CT5.241 3-PHASE, 24V, 5A, 120W CT-Series 22. APPLICATION NOTES 22.1. PEAK CURRENT CAPABILITY The unit can deliver peak currents (up to several milliseconds) which are higher than the specified short term currents. This helps to start current demanding loads. Solenoids, contactors and pneumatic modules often have a steady state coil and a pick-up coil.
CT5.241 3-PHASE, 24V, 5A, 120W CT-Series 22.2. CHARGING OF BATTERIES The power supply can be used to charge lead-acid or maintenance free batteries. Two 12V SLA or VRLA batteries are needed in series connection. Instructions for charging batteries: a) Ensure that the ambient temperature of the power supply stays below 45°C. b) Set the output voltage, measured at no load and at the battery end of the cable, very precisely to the end-ofcharge voltage. End-of-charge voltage 27.8V 27.5V 27.15V 26.
CT5.241 3-PHASE, 24V, 5A, 120W CT-Series 22.3. SERIES OPERATION Unit A Devices of the same type can be connected in series for higher output voltages. It is possible to connect as many units in series as needed, providing the sum of the output voltage does not exceed 150Vdc. Voltages with a potential above 60Vdc must be installed with a protection against touching. Avoid return voltage (e.g. from a decelerating motor or battery) which is applied to the output terminals.
CT5.241 3-PHASE, 24V, 5A, 120W CT-Series 22.5. PARALLEL USE FOR REDUNDANCY 1+1 Redundancy: Devices can be paralleled for redundancy to gain higher system availability. Redundant systems require a certain amount of extra power to support the load in case one device fails. The simplest way is to put two devices in parallel. This is called a 1+1 redundancy. In case one device fails, the other one is automatically able to support the load current without any interruption.
CT5.241 3-PHASE, 24V, 5A, 120W CT-Series 22.6. USE IN A TIGHTLY SEALED ENCLOSURE When the device is installed in a tightly sealed enclosure, the temperature inside the enclosure will be higher than outside. In such situations, the inside temperature defines the ambient temperature for the device. In the following test setup, the device is placed in the middle of the box, no other heat producing items are inside the box. The load is placed outside the box.
CT5.241 3-PHASE, 24V, 5A, 120W CT-Series 22.7. MOUNTING ORIENTATIONS Mounting orientations other than input terminals on the bottom and output on the top require a reduction in continuous output power or a limitation in the maximum allowed ambient temperature. The listed lifetime and MTBF values from this datasheet apply only for the standard mounting orientation. The following curves give an indication for allowed output currents for altitudes up to 2000m (6560ft). Fig.