Datasheet
CT5.241
CT-Series
3-PHASE, 24V, 5A, 120W
8. EFFICIENCY AND POWER LOSSES
AC 400V AC 480V
Efficiency Typ. 90.4% 90.0% At 24V, 5A
Average efficiency *) Typ. 88.8% 87.9% 25% at 1.25A, 25% at 2.5A, 25% at 3.75A.
25% at 5A
Power losses Typ. 1.5W 1.6W At 0A
Typ. 7.5W 7.7W At 24V, 2.5A
Typ. 12.7W 13.3W At 24V, 5A
Typ. 15.3W 15.8W At 24V, 6A
*) The average efficiency is an assumption for a typical application where the power supply is loaded with 25% of the nominal load for 25%
of the time, 50% of the nominal load for another 25% of the time, 75% of the nominal load for another 25% of the time and with 100%
of the nominal load for the rest of the time.
Fig. 8-1 Efficiency vs. output current at 24V,
typ.
Fig. 8-2 Losses vs. output current at 24V,
typ.
Efficiency
9/27
1
86
88
90
85
91%
6A245
Output Current
3
87
89
4
0
0
V
a
c
480Vac
Power Losses
012 456A
0
3
9
15
18W
400Vac
480Vac
6
3
12
Output Current
Fig. 8-3 Efficiency vs. input voltage at 24V,
5A, typ.
Fig. 8-4 Losses vs. input voltage at 24V, 5A,
typ.
Efficiency
320 360 400 440 480
91%
88.5
89.5
90.5
90.0
89.0
88.0
520 560
Input Voltage Vac
Power Losses
320 360 400 440 480
18W
3
9
15
12
6
o
520 560
Input Voltage Vac
May 2018 / Rev. 2.0 DS-CT5.241-EN All values are typical figures specified at 400Vac, 50Hz input voltage, 24V, 5A output load,
25°C ambient and after a 5 minutes run-in time unless otherwise noted.