Datasheet
CT5.241
CT-Series
3-PHASE, 24V, 5A, 120W
May 2018 / Rev. 2.0 DS-CT5.241-EN All values are typical figures specified at 400Vac, 50Hz input voltage, 24V, 5A output load,
25°C ambient and after a 5 minutes run-in time unless otherwise noted.
www.pulspower.com Phone +49 89 9278 0 Germany
22.7. MOUNTING ORIENTATIONS
Mounting orientations other than input terminals on the bottom and output on the top require a reduction in
continuous output power or a limitation in the maximum allowed ambient temperature.
The listed lifetime and MTBF values from this datasheet apply only for the standard mounting orientation.
The following curves give an indication for allowed output currents for altitudes up to 2000m (6560ft).
Fig. 22-5
Mounting
Orientation A
(Standard
orientation)
Power
Supply
OUTPUT
Allowed Output Current at 24V
0
+45 +70°C
3.8A
5A
6A
INPUT
Ambient Temperature
+60
Fig. 22-6
Mounting
Orientation B
(Upside down)
Power
Supply
OUTPUT
INPUT
Allowed Output Current at 24V
0
+30 +70°C
4A
6A
Ambient Temperature
+60
Fig. 22-7
Mounting
Orientation C
(Table-top
mounting)
Allowed Output Current at 24V
0
+25 +70°C
3.5A
6A
Ambient Temperature
+60
Fig. 22-8
Mounting
Orientation D
(Horizontal cw)
Power
Supply
OUTPUT
INPUT
Allowed Output Current at 24V
0
+25 +70°C
3.5A
6A
Ambient Temperature
+60
Fig. 22-9
Mounting
Orientation E
(Horizontal ccw)
Power
Supply
OUTPUT
INPUT
Allowed Output Current at 24V
0
+25 +70°C
3.5A
6A
Ambient Temperature
+60
27/27