Datasheet
CT5.241
CT-Series
3-PHASE, 24V, 5A, 120W
17. DIELECTRIC STRENGTH
The output voltage is floating and has no ohmic connection to the ground.
The output is insulated to the input by a double or reinforced insulation.
Type and routine tests are conducted by the manufacturer. Field tests may be conducted in the field using the
appropriate test equipment which applies the voltage with a slow ramp (2s up and 2s down). Connect all input-
terminals together as well as all output poles before conducting the test. When testing, set the cut-off current settings
to the value in the table below.
Fig. 17-1 Dielectric strength
A B C
Type test 60s 2500Vac 3000Vac 500Vac
Routine test 5s 2500Vac 2500Vac 500Vac
Field test 5s 2000Vac 2000Vac 500Vac
Cut-off current setting > 5mA > 5mA > 15mA
A
C
B
L1
Input
Earth
Output
-
+
L2
It is recommend that either the + pole, the – pole or any other part
of the output circuit shall be connected to the earth/ground
system. This helps to avoid situations in which a load starts
unexpectedly or can not be switched off when unnoticed earth
faults occur.
May 2018 / Rev. 2.0 DS-CT5.241-EN All values are typical figures specified at 400Vac, 50Hz input voltage, 24V, 5A output load,