Datasheet

CT5.241
CT-Series
3-PHASE, 24V, 5A, 120W
14. EMC
The EMC behavior of the device is designed for applications in industrial environment as well as in residential,
commercial and light industry environments. The output is allowed to be grounded or floating.
The device is investigated according to the generic standards EN 61000-6-1, EN 61000-6-2, EN 61000-6-3 and EN 61000-
6-4.
EMC Immunity
Electrostatic discharge EN 61000-4-2 Contact discharge
Air discharge
8kV
15kV
Criterion A
Criterion A
Electromagnetic RF field EN 61000-4-3 80MHz-2.7GHz 10V/m Criterion A
Fast transients (Burst) EN 61000-4-4 Input lines
Output lines
4kV
2kV
Criterion A
Criterion A
Surge voltage on input EN 61000-4-5
L1 Æ L2
L1 Æ PE, L2 Æ PE
2kV
4kV
Criterion A
Criterion A
Surge voltage on output EN 61000-4-5 + Æ -
+ / - Æ PE
500V
1kV
Criterion A
Criterion A
Conducted disturbance EN 61000-4-6 0.15-80MHz 10V Criterion A
Mains voltage dips EN 61000-4-11 0% of 380Vac
0% of 480Vac
0Vac, 20ms
0Vac, 20ms
Criterion A
Criterion A
Mains voltage dips EN 61000-4-11 40% of 380Vac
40% of 480Vac
70% of 380Vac
70% of 480Vac
200ms
200ms
500ms
500ms
Criterion C
Criterion C
Criterion A
Criterion A
Voltage interruptions EN 61000-4-11 5s Criterion C
Powerful transients VDE 0160 over entire load range 1550V, 1.3ms Criterion A
Criterions:
A: The device shows normal operation behavior within the defined limits.
C: Temporary loss of function is possible. The device may shut down and restarts by itself. No damage or hazards for the device will occur.
EMC Emission
Conducted emission
input lines
EN 55011, EN 55022, FCC Part 15, CISPR 11, CISPR 22 Class B
Conducted emission
output lines
IEC/CISPR 16-1-2, IEC/CISPR 16-2-1 Limits for local DC power
networks fulfilled
Radiated emission EN 55011, EN 55022 Class B
Harmonic input current EN 61000-3-2 Fulfilled for Class A equipment
Voltage fluctuations, flicker EN 61000-3-3 Fulfilled, tested with constant
current loads, non pulsing
This device complies with FCC Part 15 rules.
Operation is subjected to following two conditions: (1) this device may not cause harmful interference, and (2) this
device must accept any interference received, including interference that may cause undesired operation.
Switching Frequency
Main converter 45kHz to 170kHz Output load and input voltage dependent
May 2018 / Rev. 2.0 DS-CT5.241-EN All values are typical figures specified at 400Vac, 50Hz input voltage, 24V, 5A output load,
25°C ambient and after a 5 minutes run-in time unless otherwise noted.
www.pulspower.com Phone +49 89 9278 0 Germany
13/27