Datasheet
CT5.241
CT-Series
3-PHASE, 24V, 5A, 120W
11. CONNECTION TERMINALS
The terminals are IP20 Finger safe constructed and suitable for field- and factory wiring.
Input Output
Type Screw termination Screw termination
Solid wire Max. 6mm
2
Max. 6mm
2
Stranded wire Max. 4mm
2
Max. 4mm
2
American Wire Gauge AWG 20-10 AWG 20-10
Max. wire diameter (including ferrules) 2.8mm 2.8mm
Recommended tightening torque 1Nm, 9lb-in 1Nm, 9lb-in
Wire stripping length 7mm / 0.28inch 7mm / 0.28inch
Screwdriver 3.5mm slotted or Phillips No 1 3.5mm slotted or Phillips No 1
Daisy chaining:
Daisy chaining (jumping from one power supply output to the next) is allowed as long as the average output current
through one terminal pin does not exceed 25A. If the current is higher, use a separate distribution terminal block as
shown in Fig. 11-2.
Fig. 11-1 Daisy chaining of outputs Fig. 11-2 Using distribution terminals
Load
+
-
Power
Supply
+ +
- -
Output
Power
Supply
+ +
- -
Output
max 25A!
continuous
Distribution
Terminals
Load
+
-
Power
Supply
+ +
- -
Output
Power
Supply
+ +
- -
Output
May 2018 / Rev. 2.0 DS-CT5.241-EN All values are typical figures specified at 400Vac, 50Hz input voltage, 24V, 5A output load,
25°C ambient and after a 5 minutes run-in time unless otherwise noted.