Datasheet

CT5.241
CT-Series
3-PHASE, 24V, 5A, 120W
P
OWER SUPPLY
AC 380-480V Wide-range Input
Input Fuses Already Included
Requires only Two Legs of a 3-Phase System
Width only 40mm
Efficiency up to 90.4%
20% Output Power Reserves
Input -Transient Blanking Circuit Included
Minimal Inrush Current Surge
Full Power Between -25°C and +60°C
3 Year Warranty
1/27
PRODUCT DESCRIPTION
The Dimension C-Series are cost optimized power
supplies without compromising quality, reliability and
performance. The C-Series is part of the DIMENSION
power supply family. The most outstanding features of
CT5.241 are the high efficiency, electronic inrush current
limitation, active input transient filter and wide
operational temperature range, the small size and other
technological design concepts.
The C-Series includes all the essential basic functions.
The devices have a power reserve of 20% included,
which may even be used continuously at temperatures
up to +45°C. The CT5.241 utilizes only 2 legs of a 3-
phase system which saves wiring and installation costs.
Furthermore, this allows a smaller unit without
compromising the size of the terminals. Due to the low
power consumption, an unbalancing of the individual
phases is not expected.
SHORT-FORM DATA
Output voltage DC 24V Nominal
Adjustment range 24 - 28V Factory setting 24.1V
Output current 6.0 – 5.1A Below +45°C ambient
5.0 – 4.3A At +60°C ambient
3.8 – 3.2A At +70°C ambient
Derate linearly between +45°C and +70°C
Input voltage AC AC 380-480V -15%/+20%
Mains frequency 50-60Hz ±6%
Input current AC 0.75 / 0.68A At 400 / 480Vac
Power factor 0.45 / 0.43 At 400 / 480Vac
AC Inrush current 4 / 4Apk At 400 / 480Vac
Efficiency 90.4 / 90.0% At 400 / 480Vac
Losses 12.7 / 13.3W At 400 / 480Vac
Hold-up time 40 / 60ms At 400 / 480Vac
Temperature range -25°C to +70°C
Size (WxHxD) 40x124x117mm Without DIN-rail
Weight 500g / 1.1lb
ORDER NUMBERS
Power Supply CT5.241
Mechanical Accessory
ZM1.WALL Wall/panel mount bracket
ZM12.SIDE Side mount bracket
MAIN APPROVALS
For details or a complete approval list see section 18.
IND. CONT. EQ.
UL 508
UL 60950-1
May 2018 / Rev. 2.0 DS-CT5.241-EN All values are typical figures specified at 400Vac, 50Hz input voltage, 24V, 5A output load,
25°C ambient and after a 5 minutes run-in time unless otherwise noted.
www.pulspower.com Phone +49 89 9278 0 Germany