Datasheet
CT5.121
CT-Series
3-PHASE, 12V, 8A, 96W
22. APPLICATION NOTES
22.1. PEAK CURRENT CAPABILITY
The unit can deliver peak currents (up to several milliseconds) which are higher than the specified short term currents.
This helps to start current demanding loads. Solenoids, contactors and pneumatic modules often have a steady state
coil and a pick-up coil. The inrush current demand of the pick-up coil is several times higher than the steady-state
current and usually exceeds the nominal output current (including the PowerBoost). The same situation applies when
starting a capacitive load.
The peak current capability also ensures the safe operation of subsequent circuit breakers of load circuits. The load
branches are often individually protected with circuit breakers or fuses. In case of a short or an overload in one branch
circuit, the fuse or circuit breaker need a certain amount of over-current to open in a timely manner. This avoids
voltage loss in adjacent circuits.
The extra current (peak current) is supplied by the power converter and the built-in large sized output capacitors of
the power supply. The capacitors get discharged during such an event, which causes a voltage dip on the output. The
following examples show typical voltage dips for resistive loads:
Fig. 22-1 16A peak current for 50ms, typ.
(2x the nominal current)
Fig. 22-2 40A peak current for 5ms, typ.
(5x the nominal current)
21/24
10ms/DIV
Output
Voltage
Output
Current
12V
16A
7V
Output
Voltage
Output
Current
12V
0A
0A
1ms/DIV
40A
3.7V
Peak current voltage dips Typ. from 12V to 7V At 16A for 50ms, resistive load
Typ. from 12V to 7V At 40A for 2ms, resistive load
Typ. from 12V to 3.7V At 40A for 5ms, resistive load
May 2018 / Rev. 2.0 DS-CT5.121-EN All values are typical figures specified at 400Vac, 50Hz input voltage, 12V, 8A output load,
25°C ambient and after a 5 minutes run-in time unless otherwise noted.
www.pulspower.com Phone +49 89 9278 0 Germany