Datasheet

CT10.241
C-Series
24V, 10A, THREE PHASE INPUT
6. OUTPUT
Output voltage nom. 24V
Adjustment range min. 24-28V guaranteed
max. 30V at clockwise end position of potentiometer
Factory setting typ. 24.1V ±0.2%, at full load, cold unit, in “single use” mode
typ. 24.1V ±0.2%, at full load, cold unit, in “parallel use” mode
typ. 25.1V at no load, cold unit, in “parallel use” mode
Line regulation max. 10mV 3x 323-576Vac
Load regulation max. 100mV in “single use” mode: static value, 0A Æ 10A
typ. 1000mV in “parallel use” mode: static value, 0A Æ 10A,
see Fig. 6-2
Ripple and noise voltage max. 50mVpp 20Hz to 20MHz, 50Ohm
Output capacitance typ. 6 500μF
Output current nom. 12A at 24V, ambient < 45°C, see Fig. 6-1
nom. 10A at 24V, ambient < 60°C, see Fig. 6-1
nom. 10.3A at 28V, ambient < 45°C, see Fig. 6-1
nom. 8.6A at 28V, ambient < 60°C, see Fig. 6-1
Output power nom. 288W ambient < 45°C
nom. 240W ambient < 60°C
Short-circuit current min. 19A continuous, load impedance 100mOhm, see Fig. 6-1
max. 23A continuous, load impedance 100mOhm, see Fig. 6-1
min. 28A <20ms, load impedance 100mOhm, see Fig. 6-1
max. 32A <20ms, load impedance 100mOhm, see Fig. 6-1
discharge current of output capacitors not included
Fig. 6-1 Output voltage vs. output current,
typ.
Fig. 6-2 Output voltage in “parallel use”
mode, typ.
Output Voltage
(Single Use, typ.)
0
0918
4
8
12
28V
16
20
24
30
A
21123 6 15 24 27
Adjustment
Range
Output Current
Extra
current
for 20ms
Continuous
current
Factory
setting
Output Voltage
(Parallel Use, typ.)
22V
048
23V
24V
25V
29V
26V
27V
28V
12A1062
Adjustment
Range
Factory
setting
Output Current
Peak current capability (up to several milliseconds)
The power supply can deliver a peak current which is higher than the specified short term current. This helps to start
current demanding loads or to safely operate subsequent circuit breakers.
The extra current is supplied by the output capacitors inside the power supply. During this event, the capacitors will be
discharged and causes a voltage dip on the output. Detailed curves can be found in chapter 23.1.
Peak current voltage dips typ. from 24V to 6V at 20A for 50ms, resistive load
typ. from 24V to 12V at 50A for 2ms, resistive load
typ. from 24V to 3V at 50A for 5ms, resistive load
Jan. 2010 / Rev. 1.3 DS-CT10.241-EN
All parameters are specified at 24V, 10A, 3x400Vac, 25°C ambient and after a 5 minutes run-in time unless otherwise noted.
www.pulspower.com Phone +49 89 9278 0 Germany
6/22