Datasheet
CT10.241, CT10.241-C1
CT-Series
3-PHASE, 24V, 10A, 240W
May 2018 / Rev. 2.0a DS-CT10.241-EN All values are typical figures specified at 3x 400Vac, 50Hz input voltage, symmetrical
phase voltages, 24V, 10A output load, 25°C ambient and after a 5 minutes run-in time unless otherwise noted.
www.pulspower.com Phone +49 89 9278 0 Germany
8/28
Fig. 6-1 Output voltage vs. output current,
typ.
Fig. 6-2 Output voltage in “parallel use”
mode, typ.
Output Voltage (Single Use, typ.)
0
0 9
18
4
8
12
28V
16
20
24
30A21123
6 15
24 27
Adjustment
Range
Output Current
Extra
current
for 20ms
Continuous
current
Factory
setting
Output Voltage (Parallel Use, typ.)
22V
0 4 8
23V
24V
25V
29V
26V
27V
28V
12A
1062
Adjustment
Range
Factory
setting
Output Current
7. H
OLD
-
UP
T
IME
3AC 400V 3AC 480V
Hold
-up Time Typ. 34ms 54ms At 24V, 10A, see Fig. 7-1
Typ. 68ms 108ms At 24V, 5A, see Fig. 7-1
Min 28ms 44ms At 24V, 10A, see Fig. 7-1
Min. 56ms 87ms At 24V, 5A, see Fig. 7-1
Fig. 7-1 Hold-up time vs. input voltage Fig. 7-2 Shut-down behavior, definitions
0
20
40
60
100ms
320 360
400 440 3x480Vac
Input Voltage
Hold-up Time at 24Vdc
5A, typ.
10A, typ.
10A, min.
5A, min.
80
- 5%
Hold-up Time
Output
Voltage
Input
Voltage
L1 L2 L3