Datasheet

CS5.244
CSeries
24V, 5A, SINGLE PHASE INPUT
Dec. 2006 / Rev. 1.1 DS-CS5.244-EN
All parameters are specified at 24V, 5A, 230Vac, 25°C ambient and after a 5 minutes run-in time unless otherwise noted.
www.pulspower.com Phone +49 89 9278 0 Germany
5/20
8. HOLD-UP TIME
AC 100V AC 120V AC 230V
Hold-up Time typ. - - 161ms 2,5A, 24V, see
Fig. 8-1
typ. - - 78ms 5A, 24V, see Fig. 8-1
typ. - - 63ms 6A, 24V, see
Fig. 8-1
Fig. 8-1 Hold-up time vs. input voltage Fig. 8-2 Shut-down behavior, definitions
0
25
50
170 200 230 264Vac
Hold-up
Time
100
75
125
Input Voltage
a) 24V 2.5A typ.
b) 24V 2.5A min.
c) 24V 5A typ.
d) 24V 5A min.
e) 24V 6A min.
a
b
c
d
e
150ms
- 5%
Hold-up Time
Zero Transition
Output
Voltage
Intput
Voltage
Note: At no load, the hold-up time can be up to several seconds. The green DC-ok lamp is on during this time.