Datasheet

CS5.244
C-Line
24V, 5A, SINGLE PHASE INPUT
3. AC-INPUT
AC input nom. AC 200-240V ±10%
Mains network systems TN, TT or IT
AC input range min. 180-264Vac
264-300Vac
continuous operation
max. 500ms
Allowed voltage L or N to earth max. 300Vac continuous, IEC 62103
Input frequency nom. 50–60Hz ±6%
Turn-on voltage typ. 105Vac steady-state value, see Fig. 3-1
Shut-down voltage typ. 95Vac steady-state value, see Fig. 3-1
Input current typ. 1.16A at 24V, 5A, see Fig. 3-3
Power factor
*)
typ. 0.5 at 24V, 5A, see Fig. 3-4
Crest factor
**)
typ. 3.7 at 24V, 5A
Start-up delay typ. 130ms see Fig. 3-2
Rise time typ. 8ms at 24V, 5A const. current load, 0mF load capacitance, see
Fig. 3-2
typ. 25ms at 24V, 5A const. current load, 5mF load capacitance,,
see Fig. 3-2
Turn-on overshoot max. 400mV see Fig. 3-2
External input protection See recommendations in chapter 22.3.
*) The power factor is the ratio of the true (or real) power to the apparent power in an AC circuit.
**) The crest factor is the mathematical ratio of the peak value to RMS value of the input current waveform.
Fig. 3-1 Input voltage ranges Fig. 3-2 Turn-on behavior, definitions
Turn-on
180
V
IN
P
OUT
300Vac
Shut-down
264
Rated Input
Range
Start-up
delay
Rise
Time
Overshoot
- 5%
Output
Voltage
Input
Voltage
Fig. 3-3 Input current vs. output load at 24V Fig. 3-4 Power factor vs. output load
6A
1
1.5 2 3
4
0
0.5
1.0
1.5
2A
5
Output Current
2.5
3.5
4.5
5.5
Input Current, typ.
6A
1
1.5 2 3
4
0.35
0.40
5
Output Current
2.5
3.5
4.5
5.5
0.45
0.50
0.55
0.60
0.65
Power Factor, typ.
Jul. 2015 / Rev. 2.0 DS-CS5.244-EN
All parameters are specified at 24V, 5A, 230Vac, 50Hz, 25°C ambient and after a 5 minutes run-in time unless otherwise noted.
www.pulspower.com Phone +49 89 9278 0 Germany