User manual

C-Series Power Supply Instruction Manual
Environment
Protection
Operational temperature -25 to +70°C De-rate above +60°C Output Overload, no-load, short-circuit proof
Storage temperature -40 to +85° C Storage, transport Degree of protection IP 20 EN/IEC 60529
Humidity < 95% r .H. IEC 60068-2-30 Class of protection I PE (Ground) connection required!
Do not energize while condensation is present
Over-voltage category III EN 50178
Vibration sinusoidal 2g IEC 60068-2-6 Degree of pollution 2 EN 50178, not conductive
Shock 30g 6ms, 20g 11ms IEC 60068-2-27 Over-temperature protection yes Output shut-down with automatic restart
Output over-voltage protection yes Output shut-down with automatic restart
Penetration protection >3.5mm e.g. screws, small parts …
Internal input fuse
(Device protection, not externally
accessible, IEC 60127-2/5, HBC)
T4A
T6A3
CS5
CS10
Allowed output current versus
the ambient temperature
Ambient temperature is defined
2cm below the unit.
Please note:
The CS5 units can respond with a
thermal shut-down when
continuously loaded with more than
120W and operated with a mains
voltage of 100V or below.
Allowable Output
Cur re nt
0
-25 0 20 40
70°
C
2
4
60
80
100
120%
60
Ambient Temperature
c
o
n
t
i
n
u
o
u
s
s
h
o
r
t
t
e
r
m
External fuse on input side
The unit is tested and approved for branch circuits up to 20A. External protection is only
required if the supplying branch has an ampacity greater than this. In some countries local
regulations might apply. Check also local codes and local requirements. If an external fuse is
necessary or utilized, minimum requirements need to be considered. To avoid a wrong
tripping of the circuit breaker, a minimum value of:
B10A or C6A for CS5.241, CS10.241, CS10.241, CS10.242 and
B16A or C10A for CS5.2413, CS5.244, CS10.243, CS10.244 is required.
Safety Terminals and Connections
Type Screw Terminals Separation of output
SELV
PELV
IEC/EN 60950-1
EN 60204-1, EN 50178, IEC 60364-4-41
Solid wire 0.5-6mm
2
Stranded wire 0.5-4mm
2
American wire gauge 20-10 AWG
Touch current
CS5: <0.7mA
CS10: <0.7mA
Earth leakages current, TN- mains
Ferrules allowed, but not required
Stripping length 7mm / 0.275inch Isolation resistance
PE resistance
min. 5MOhm
max. 0.1Ohm
Input to output, 500Vdc
Between housing and ground terminal
Screwdriver 3.5mm slotted or Philips No 2
Transformer Safety transformer IEC/EN 61558-2-17 Recommended tightening torque 0.8Nm, 7lb.in
Approvals See datasheet or markings on the unit
Use appropriate copper cables that are designed for an operating temperatures of 60°C (for
ambient up to 45°C) and 75°C (for ambient up to 60°C), minimum. Follow national installation
codes and regulations! Ensure that all strands of a stranded wire enter the terminal connection!
Up to two stranded wires with the same cross section are permitted in one connection point
(except PE wire). Do not use without PE (Ground) connection!
EMC
CS5.243, CS5.244, CS10.242, CS10.243:
These devices are suitable for applications in industrial environment as well as in residential,
commercial and light industry environment without any restrictions.
For further details see datasheet.
EMC
CS5.241, CS10.241, CS10.244, CS10.481:
These devices are suitable for applications in industrial environment without any restrictions.
For further details see datasheet.
EMC Immunity EN 61000-6-1, EN 61000-6-2 EMC Immunity EN 61000-6-1, EN 61000-6-2
EMC Emission EN 61000-3-2, EN 61000-3-3, EN 61000-6-3, EN 61000-6-4,
FCC Part 15 Class B
EMC Emission EN 61000-3-3, EN 61000-6-4, FCC Part 15 Class B
FCC
This device complies with FCC Part 15 rules. Operation is subjected to following two conditions: (1) this device may not cause harmful interference, and (2) this device must accept any
interference received, including interference that may cause undesired operation.
CE mark is in conformance with EMC guideline 89/336/EEC and 93/68/EEC and the low-voltage directive (LVD) 73/23/EWG.
Physical Dimensions, Weight and
Cooling
Weight
500g / 1.1lb CS5.xxx
700g / 1.54lb CS10.241
CS10.243
CS10.244
CS10.481
800g / 1.76lb CS10.242
DIN-Rail
Use DIN-rails according to EN 60715 or
EN 50022 with a height of 7.5 or 15mm
Mounting Orientation
Output terminal on top and input terminals
on the bottom.
For other orientations see datasheet.
CS5 CS10 CS5, CS10
Do not obstruct air flow!
The unit is convection cooled. Ventilation grid must be kept free of any obstructions.
Keep installation clearances at higher ambient temperature and full load:
40mm on top, 20mm on the bottom, 5mm on the left and right side are recommended when loaded permanently with full power. In case the adjacent device is a heat source, 15mm clearance
are recommended.