12. FRONT SIDE AND USER ELEMENTS
Fig. 12-1 Front side
Output voltage potentiometer
Open the flap to tune the output voltage.
Factory set: 24.1V
Output Terminals
Screw terminals
(Spring-clamp terminals on the
CS5.241-S1)
+ Positive output
- Negative (return) output
Dual pins per pole
Input Terminals
Screw terminals
(Spring-clamp terminals
on the CS5.241-S1)
N … Neutral input
L … Line (hot) input
... PE (Protective Earth) input
DC-on lamp (green)
On when the voltage on the output
terminals is > 21 V
13. TERMINALS AND WIRING
Type Screw terminals (CS5.241, CS5.241-C1), ); Spring-clamp terminals (CS5.241-S1)
Solid wire 0.5-6mm
2
Stranded wire 0.5-4mm
2
American wire gauge 20-10 AWG
Ferrules allowed, but not required
Wire stripping length 7mm / 0.275inch
Screwdriver 3.5mm slotted or Pozidrive No 2 (only for screw terminals)
Recommended tightening torque 0.8Nm, 7lb.in (only for screw terminals)
Instructions:
a) Use appropriate copper cables that are designed for an operating temperature of:
60°C for ambient up to 45°C and
75°C for ambient up to 60°C minimum.
b) Follow national installation codes and installation regulations!
c) Ensure that all strands of a stranded wire enter the terminal connection!
d) Up to two stranded wires with the same cross section are permitted in one connection point (except PE wire).
e) Do not use the unit without PE connection.