5. AC-INPUT
AC input
nom. AC 100-120V /
200-240V
auto-select input, TN-, TT-, IT-Mains, see Fig. 5-1
AC input range 90-132Vac 100-120V range, continuous operation
180-264Vac 200-240V range, continuous operation
85-90Vac Short term or with output derating
264-300Vac < 0.5s
Input frequency nom. 50 – 60Hz ±6%
AC 100V AC 120V AC 230V
Input current typ. 2.34A 2.05A 1.23A at 24V, 5A see Fig. 5-3
Power factor *) typ. 0.58 0.56 0.47 at 24V, 5A see Fig. 5-1
Crest factor **) typ. 2,9 3,1 3,7 at 24V, 5A
Start-up delay
typ. 740ms 900ms 720ms see Fig. 5-2
Rise time typ. 8ms 8ms 8ms 0mF, 24V, 5A, see Fig. 5-2
typ. 25ms 25ms 25ms 5mF, 24V, 5A, see Fig. 5-2
Turn-on overshoot
max. 400mV 400mV 400mV see Fig. 5-2
Turn-on voltage typ. 75Vac 75Vac N / A steady-state value, see Fig. 5-1
Shut-down voltage typ. 55Vac 55Vac N / A steady-state value, see Fig. 5-1
*) The power factor is the ratio of the true (or real) power to the apparent power in an AC circuit.
**) The crest factor is the mathematical ratio of the peak value to the RMS value of the input current waveform
Fig. 5-1 Input voltage range Fig. 5-2 Turn-on behavior, definitions
Turn-on
90V
Rated input ranges
V
IN
P
OUT
264Vac180V
Shut-down
132V
no
harm
from
132 to
180V
Range
100-
120V
Range
200-
240V
Start-up
delay
Rise
Time
Overshoot
- 5%
Output
Voltage
Intput
Voltage
Fig. 5-3 Input current vs. output load Fig. 5-4 Power Factor vs. output load
6A
1
1.5 2 3
4
0
0.5
1
1.5
2
2.5
3A
Input
Current, typ.
5
Output Current
2.5
3.5
4.5
5.5
2
3
0
V
a
c
1
2
0
V
a
c
1
0
0
V
a
c
6A
1
1.5 2 3
4
0.35
0.4
5
Output Current
2.5
3.5
4.5
5.5
0.45
0.5
0.55
0.6
0.65
Power Factor, typ.
2
3
0
V
a
c
1
2
0
V
a
c
1
0
0
V
a
c