Datasheet

CS5.241, CS5.241-C1, CS5.241-S1
C-Line
24V, 5A, SINGLE PHASE INPUT
6. OUTPUT
Output voltage nom. 24V
Adjustment range min. 24-28V guaranteed
max. 30V
***)
at clockwise end position of potentiometer
Factory settings typ. 24.1V ±0.2%, at full load, cold unit,
Line regulation max. 70mV 90-132 / 180-300Vac
Load regulation max. 100mV static value, 0A Æ 5A; see Fig. 6-1
Ripple and noise voltage max. 50mVpp 20Hz to 20MHz, 50Ohm
Output current nom. 5A at 24V, ambient temperature <60°C, see Fig. 6-1
nom. 6A
*)
at 24V, ambient temperature <45°C
nom. 3.75A at 24V and 70°C ambient temperature
nom. 4.3A at 28V, ambient temperature <60°C, see Fig. 6-1
nom. 5.1A
*)
at 28V, ambient temperature <45°C, see Fig. 6-1
nom. 3.2A at 28V and 70°C ambient temperature
Reduce output current linearly between +45°C and +70°C
Output power nom. 120W continuously available
nom. 144W
*)
Power Boost
® *)
Overload behavior continuous current see Fig. 6-1
Short-circuit current min. 10A
**)
load impedance <200mOhm, see Fig. 6-1
max. 14A
**)
load impedance <200mOhm, see Fig. 6-1
Output capacitance typ. 1 800μF included inside the power supply
*) Power Boost
This power/ current is continuously allowed up to an ambient temperature of 45°C.
Above 45°C, do not use this power/ current longer than a duty cycle of 10% and/ or not longer than 1 minute every 10 minutes.
**) Discharge current of output capacitors is not included.
***) This is the maximum output voltage which can occur at the clockwise end position of the potentiometer due to tolerances. It is not a
guaranteed value which can be achieved. The typical value is about 28.5V.
Fig. 6-1 Output voltage vs. output current,
typ.
Output Voltage
0
048
4
8
12
28V
16
20
24
12A1062
Adjustment
Range
Output Current
Jul. 2015 / Rev. 2.0 DS-CS5.241-EN
All parameters are specified at 24V, 5A, 230Vac, 50Hz, 25°C ambient and after a 5 minutes run-in time unless otherwise noted.
www.pulspower.com Phone +49 89 9278 0 Germany
8/25