Datasheet
CS5.241, CS5.241-C1, CS5.241-S1
C-Line
24V, 5A, SINGLE PHASE INPUT
4. DC-INPUT
Do not operate this power supply with DC-input voltage. Use the QS5.241 unit instead.
5. INPUT INRUSH CURRENT
After turn-on of the input voltage, an active inrush limitation circuit limits the input inrush current. Virtually no input
inrush current is generated.
The charging current into the EMI suppression capacitors is disregarded in the first microseconds after switch-on.
AC 100V AC 120V AC 230V
Inrush current max. 10A
peak
10A
peak
10A
peak
temperature independent
typ. 3A
peak
3A
peak
3A
peak
temperature independent
Inrush energy max. 1A
2
s 1A
2
s 1A
2
s temperature independent
Fig. 5-1 Typical input inrush current behavior
Input Current
Input Voltage
Output Voltage
Input: 230Vac
Output: 24V, 5A
Ambient: 25°C
Upper curve: Input current (10A / DIV)
Medium curve: Input voltage (500V / DIV)
Lower curve: Output voltage (20V / DIV)
Time scale: 100ms / DIV
Jul. 2015 / Rev. 2.0 DS-CS5.241-EN
All parameters are specified at 24V, 5A, 230Vac, 50Hz, 25°C ambient and after a 5 minutes run-in time unless otherwise noted.
www.pulspower.com Phone +49 89 9278 0 Germany
7/25