Datasheet

CS5.241, CS5.241-C1, CS5.241-S1
C-Line
24V, 5A, SINGLE PHASE INPUT
3. AC-INPUT
AC input nom. AC 100-120V /
200-240V ±10%
Auto-select input
Mains network systems TN, TT or IT
90-132Vac /
180-264Vac
85-90Vac
264-300Vac
continuous operation, lower input voltage range
continuous operation, upper input voltage range
short-tem or with reduced output current, see Fig. 3-5
max. 500ms
AC input range min.
no harm to the power supply with input voltages between 132 and 180Vac
Allowed voltage L or N to earth max. 300Vac continuous, IEC 62103
Input frequency nom. 50–60Hz ±6%
Turn-on voltage typ. 75Vac steady-state value, see Fig. 3-1
Shut-down voltage typ. 55Vac steady-state value, see Fig. 3-1
External input protection See recommendations in chapter 22.3.
AC 100V AC 120V AC 230V
Input current typ. 2.33A 2.0A 1.23A at 24V, 5A, see Fig. 3-3
Power factor
*)
typ. 0.58 0.56 0.47 at 24V, 5A, see Fig. 3-4
Crest factor
**)
typ. 2.9 3.1 3.7 at 24V, 5A
Start-up delay typ. 740ms 900ms 720ms see Fig. 3-2
Rise time typ. 8ms 8ms 8ms at 24V, 5A const. current load, 0mF
load capacitance, see Fig. 3-2
typ. 25ms 25ms 25ms at 24V, 5A const. current load, 5mF
load capacitance,, see Fig. 3-2
Turn-on overshoot max. 400mV 400mV 400mV see Fig. 3-2
*) The power factor is the ratio of the true (or real) power to the apparent power in an AC circuit.
**) The crest factor is the mathematical ratio of the peak value to RMS value of the input current waveform.
Fig. 3-1 Input voltage ranges Fig. 3-2 Turn-on behavior, definitions
Turn-on
(85) 90
Rated input ranges
V
IN
P
OUT
264180
Shut-down
132
Upper
range
Lower
range
300Vac
max.
500ms
Start-up
delay
Rise
Time
Overshoot
- 5%
Output
Voltage
Input
Voltage
Jul. 2015 / Rev. 2.0 DS-CS5.241-EN
All parameters are specified at 24V, 5A, 230Vac, 50Hz, 25°C ambient and after a 5 minutes run-in time unless otherwise noted.
www.pulspower.com Phone +49 89 9278 0 Germany