User manual
CS10.481
C–Series
48V, 5A, SINGLE PHASE INPUT
Nov. 2006 / Rev.1.1 DS-CS10.481-EN
All parameters are specified at 48V, 5A, 230Vac, 25°C ambient and after a 5 minutes run-in time unless otherwise noted.
www.pulspower.com Phone +49 89 9278 0 Germany
7/20
10. FUNCTIONAL DIAGRAM
Fig. 10-1 Functional diagram
+
+
-
-
V
OUT
Input Fuse
&
Input Filter
Output
Voltage
Regulator
Power
Converter
Output
Filter
DC
ok
L
N
Output
Over-
Voltage
Protection
Input
Rectifier
&
Inrush
Limiter
115/230V
Auto Select
11. RELIABILITY
AC 100V AC 120V AC 230V
Lifetime expectancy min. 45 000h 60 000h 96 000h 40°C, 48V, 5A
min. 33 000h 42 000h 63 000h 40°C, 48V, 6A
min. 97 000h 106 000h 122 000h 40°C, 48V, 2.5A
min. 126 000h 15 years 15 years 25°C, 48V, 5A
MTBF SN 29500, IEC 61709 627 000h 653 000h 830 000h 40°C, 48V, 5A
536 000h 558 000h 709 000h 40°C, 48V, 6A
1 060 000h 1 104 000h 1 403 000h 25°C, 48V, 5A
MTBF MIL HDBK 217F 459 000h 450 000h 475 000h 40°C, 48V, 5A, Ground Benign GB40
413 000h 406 000h 426 000h 40°C, 48V, 6A, Ground Benign GB40
655 000h 642 000h 659 000h 25°C, 48V, 5A, Ground Benign GB25
The Lifetime expectancy shown in the table indicates the operating hours (service life) and is determined by the
lifetime expectancy of the built-in electrolytic capacitors.
Lifetime expectancy is specified in operational hours. Lifetime expectancy is calculated according to the capacitor’s
manufacturer specification. The prediction model allows a calculation of up to 15 years from date of shipment.
MTBF stands for Mean Time Between Failure, which is calculated according to statistical device failures, and indicates
reliability of a device. It is the statistical representation of the likelihood of a unit to fail and does not necessarily
represent the life of a product.