User manual
CS10.481
C–Series
48V, 5A, SINGLE PHASE INPUT
Nov. 2006 / Rev.1.1 DS-CS10.481-EN
All parameters are specified at 48V, 5A, 230Vac, 25°C ambient and after a 5 minutes run-in time unless otherwise noted.
www.pulspower.com Phone +49 89 9278 0 Germany
4/20
6. INPUT INRUSH CURRENT SURGE
An active inrush limitation circuitry limits the input inrush current after turn-on of the input voltage.
The charging current into EMI suppression capacitors is disregarded in the first milliseconds after switch-on.
AC 100V AC 120V AC 230V
Inrush current max. 10A
peak
10A
peak
10A
peak
-25°C to +70°C
typ. 3A
peak
3A
peak
3A
peak
-25°C to +70°C
Inrush energy
typ. 1A
2
s 1A
2
s 1A
2
s -25°C to +70°C
Fig. 6-1 Input inrush current, typical behavior
Input Current
Input Voltage
Output Voltage
A
A: Start-up delay = Inrush delay
Input: 230Vac
Output: 48V, 5A
Ambient: 25°C
Upper curve: Input current 10A / DIV
Medium curve: Input voltage 500V / DIV
Lower curve: Output voltage 40V / DIV
Time scale: 100ms / DIV
7. HOLD-UP TIME
AC 100V AC 120V AC 230V
Hold-up Time typ. 62ms 107ms 103ms 2.5A, 48V, see
Fig. 7-1
typ. 23ms 46ms 47ms 5A, 48V, see Fig. 7-1
typ. 17ms 35ms 37ms 6A, 48V, see
Fig. 7-1
Fig. 7-1 Hold-up time vs. input voltage Fig. 7-2 Shut-down behavior, definitions
0
20
40
120ms
85 120100 180 230Vac
Hold-up Time
80
60
100
Input Voltage
a) 48V 2.5A typ.
b) 48V 2.5A min.
c) 48V 5A typ.
d) 48V 5A min.
e) 48V 6A min.
a a
b
c
c
d
d
e
e
b
- 5%
Hold-up Time
Zero Transition
Output
Voltage
Intput
Voltage
Note: At no load, the hold-up time can be up to several seconds. The green DC-ok lamp is on during this time.