Datasheet

CS10.481
C-Line
48V, 5A, SINGLE PHASE INPUT
7. HOLD-UP TIME
AC 100V AC 120V AC 230V
Hold-up Time typ. 62ms 107ms 103ms at 48V, 2.5A, see Fig. 7-1
min. 50ms 86ms 83ms at 48V, 2.5A, see Fig. 7-1
typ. 23ms 46ms 47ms at 48V, 5A, see Fig. 7-1
min. 19ms 37ms 38ms at 48V, 5A, see Fig. 7-1
typ. 17ms 35ms 37ms at 48V, 6A, see Fig. 7-1
min. 14ms 28ms 30ms at 48V, 6A, see Fig. 7-1
Fig. 7-1 Hold-up time vs. input voltage Fig. 7-2 Shut-down behavior, definitions
0
20
40
120ms
85 120100 180 230Vac
Hold-up Time
80
60
100
Input Voltage
a) 48V 2.5A typ.
b) 48V 2.5A min.
c) 48V 5A typ.
d) 48V 5A min.
e) 48V 6A min.
a a
b
c
c
d
d
e
e
b
- 5%
Hold-up Time
Zero Transition
Output
Voltage
Input
Voltage
Note: At no load, the hold-up time can be up to several seconds. The green DC-OK lamp is on during this time.
Jul. 2015 / Rev. 2.0 DS-CS10.481-EN
All parameters are specified at 48V, 5A, 230Vac, 50Hz, 25°C ambient and after a 5 minutes run-in time unless otherwise noted.
www.pulspower.com Phone +49 89 9278 0 Germany
9/26