Datasheet
CS10.481
C-Line
48V, 5A, SINGLE PHASE INPUT
6. OUTPUT
Output voltage nom. 48V
Adjustment range min. 48-52V guaranteed
max. 56V
***)
at clockwise end position of potentiometer
Factory settings typ. 48.0V ±0.2%, at full load, cold unit,
Line regulation max. 70mV 90-132 / 180-300Vac
Load regulation max. 100mV static value, 0A Æ 5A; see Fig. 6-1
Ripple and noise voltage max. 100mVpp 20Hz to 20MHz, 50Ohm
Output current nom. 5A at 48V, ambient temperature <60°C, see Fig. 6-1
nom. 6A
*)
at 48V, ambient temperature <45°C
nom. 3.75A at 48V and 70°C ambient temperature
nom. 4.6A at 52V, ambient temperature <60°C, see Fig. 6-1
nom. 5.5A
*)
at 52V, ambient temperature <45°C, see Fig. 6-1
nom. 3.45A at 52V and 70°C ambient temperature
Reduce output current linearly between +45°C and +70°C
Output power nom. 240W continuously available
nom. 288W
*)
Power Boost
® *)
Overload behavior continuous current see Fig. 6-1
Short-circuit current min. 7A
**)
load impedance <100mOhm, see Fig. 6-1
max. 9A
**)
load impedance <100mOhm, see Fig. 6-1
Output capacitance typ. 3 100μF included inside the power supply
*) Power Boost
This power/ current is continuously allowed up to an ambient temperature of 45°C.
Above 45°C, do not use this power/ current longer than a duty cycle of 10% and/ or not longer than 1 minute every 10 minutes.
**) Discharge current of output capacitors is not included.
***) This is the maximum output voltage which can occur at the clockwise end position of the potentiometer due to tolerances. It is not a
guaranteed value which can be achieved. The typical value is about 54.2V.
Fig. 6-1 Output voltage vs. output current,
typ.
Output Voltage
0
02 468
10
20
60V
30
40
50
10
A
53179
Adjustment
Range
Output Current
+60°C
+25°C
-25°C
48V
52V
Jul. 2015 / Rev. 2.0 DS-CS10.481-EN
All parameters are specified at 48V, 5A, 230Vac, 50Hz, 25°C ambient and after a 5 minutes run-in time unless otherwise noted.
www.pulspower.com Phone +49 89 9278 0 Germany
8/26