Datasheet

CS10.481
C-Line
48V, 5A, SINGLE PHASE INPUT
9. LIFETIME EXPECTANCY AND MTBF
AC 100V AC 120V AC 230V
Lifetime expectancy
*)
97 000h 106 000h 122 000h at 48V, 2.5A and 40°C
275 000h
*)
299 000h
*)
346 000h
*)
at 48V, 2.5A and 25°C
45 000h 60 000h 96 000h at 48V, 5A and 40°C
128 000h 171 000h
*)
272 000h
*)
at 48V, 5A and 25°C
33 000h 42 000h 63 000h at 48V, 6A and 40°C
93 000h 119 000h 179 000h
*)
at 48V, 6A and 25°C
MTBF
**)
SN 29500, IEC 61709 627 000h 653 000h 830 000h at 48V, 5A and 40°C
536 000h 558 000h 709 000h at 48V, 6A and 40°C
1 060 000h 1 104 000h 1 403 000h at 48V, 5A and 25°C
MTBF
**)
MIL HDBK 217F 459 000h 450 000h 475 000h at 48V, 5A and 40°C;
Ground Benign GB40
413 000h 406 000h 426 000h at 48V, 6A and 40°C;
Ground Benign GB40
655 000h 642 000h 659 000h at 48V, 5A and 25°C;
Ground Bening GB25
*) The Lifetime expectancy shown in the table indicates the minimum operating hours (service life) and is determined by the lifetime
expectancy of the built-in electrolytic capacitors. Lifetime expectancy is specified in operational hours and is calculated according to the
capacitor’s manufacturer specification. The manufacturer of the electrolytic capacitors only guarantees a maximum life of up to 15 years
(131 400h). Any number exceeding this value is a calculated theoretical lifetime which can be used to compare devices.
**) MTBF stands for Mean Time Between Failure, which is calculated according to statistical device failures, and indicates reliability of a
device. It is the statistical representation of the likelihood of a unit to fail and does not necessarily represent the life of a product.
The MTBF figure is a statistical representation of the likelihood of a device to fail. A MTBF figure of e.g. 1 000 000h means that
statistically one unit will fail every 100 hours if 10 000 units are installed in the field. However, it can not be determined if the failed unit
has been running for 50 000h or only for 100h.
10. FUNCTIONAL DIAGRAM
Fig. 10-1 Functional diagram
+
+
-
-
V
OUT
Input Fuse
&
Input Filter
Output
Voltage
Regulator
Power
Converter
Output
Filter
DC
ok
L
N
Output
Over-
Voltage
Input
Rectifier
&
Inrush
Limiter
Protection
115/230V
Auto
Select
Jul. 2015 / Rev. 2.0 DS-CS10.481-EN
All parameters are specified at 48V, 5A, 230Vac, 50Hz, 25°C ambient and after a 5 minutes run-in time unless otherwise noted.
www.pulspower.com Phone +49 89 9278 0 Germany
11/26