Datasheet
CS10.244
C–Series
24V, 10A, SINGLE PHASE INPUT
Sept. 2006 / Rev. 1.0 DS-CS10.244-EN / All parameters are specified at 24V, 10A, 230Vac and 25°C ambient unless otherwise noted.
www.pulspower.com Phone +49 89 9278 0 Germany
5/21
8. HOLD-UP TIME
AC 100V AC 120V AC 230V
Hold-up Time typ. - - 102ms 5A, 24V, see
Fig. 8-1
typ. - - 45ms 10A, 24V, see Fig. 8-1
typ. - - 36ms 12A, 24V, see
Fig. 8-1
Fig. 8-1 Hold-up time vs. input voltage Fig. 8-2 Shut-down behavior, definitions
0
20
40
120ms
170 200 230 264Vac
Hold-up Time
80
60
100
Input Voltage
a) 24V 5A typ.
b) 24V 5A min.
c) 24V 10A typ.
d) 24V 10A min.
e) 24V 12A min.
a
b
c
d
e
- 5%
Hold-up Time
Zero Transition
Output
Voltage
Intput
Voltage
Note: At no load, the hold-up time can be up to several seconds. The green DC-ok lamp is on during this time.