User manual

CS10.244
CSeries
24V, 10A, SINGLE PHASE INPUT
Sept. 2006 / Rev. 1.0 DS-CS10.244-EN / All parameters are specified at 24V, 10A, 230Vac and 25°C ambient unless otherwise noted.
www.pulspower.com Phone +49 89 9278 0 Germany
3/21
5. AC-INPUT
AC input
nom. AC 200-240V TN-, TT-, IT-Mains, see Fig. 5-1
AC input range
180-264Vac continuous operation
264-300Vac < 0.5s
Input frequency nom. 50 – 60Hz ±6%
AC 100V AC 120V AC 230V
Input current typ. - - 2.2A at 24V, 10A see Fig. 5-3
Power factor *) typ. - - 0.52 at 24V, 10A see Fig. 5-1
Crest factor **) typ. - - 3,2 at 24V, 10A
Start-up delay
typ. - - 220ms see Fig. 5-2
Rise time typ. - - 35ms 0mF, 24V, 10A, see Fig. 5-2
typ. - - 75ms 10mF, 24V, 10A, see Fig. 5-2
Turn-on overshoot
max. - - 100mV see Fig. 5-2
Turn-on voltage typ. - - 155Vac steady-state value, see Fig. 5-1
Shut-down voltage typ. - - 137Vac steady-state value, see Fig. 5-1
*) The power factor is the ratio of the true (or real) power to the apparent power in an AC circuit.
**) The crest factor is the mathematical ratio of the peak value to the RMS value of the input current waveform
Fig. 5-1 Input voltage range Fig. 5-2 Turn-on behavior, definitions
Turn-on
180
V
IN
P
OUT
300Vac
Shut-down
264
200-240V
Rated Input
Range
Start-up
delay
Rise
Time
Overshoot
- 5%
Output
Voltage
Intput
Voltage
Fig. 5-3 Input current vs. output load Fig. 5-4 Power Factor vs. output load
12A
2
34567
8
9
0
0.5
1
1.5
2
2.5
3A
Input
Current, typ.
10 11
Output Current
2
3
0
V
a
c
12
A
2
34 6
8
0.35
0.4
10
Output Current
5
7
9
11
0.45
0.5
0.55
0.6
0.65
Power Factor, typ.
2
3
0
V
a
c