Datasheet
CS10.241, CS10.241-S1
C–Series
24V, 10A, SINGLE PHASE INPUT
August 2006 / Rev. 1.1 DS-CS10.241-EN / All parameters are specified at 24V, 10A, 230Vac and 25°C ambient unless otherwise noted.
www.pulspower.com Phone +49 89 9278 0 Germany
3/20
5. AC-INPUT
AC input
nom. AC 100-120V /
200-240V
auto-select input, TN-, TT-, IT-Mains, see Fig. 5-1
AC input range 90-132Vac 100-120V range, continuous operation
180-264Vac 200-240V range, continuous operation
85-90Vac Short term or with output derating
264-300Vac < 0.5s
Input frequency nom. 50 – 60Hz ±6%
AC 100V AC 120V AC 230V
Input current typ. 4.34A 3.73A 2.23A at 24V, 10A see Fig. 5-3
Power factor *) typ. 0.61 0.59 0.51 at 24V, 10A see Fig. 5-1
Crest factor **) typ. 2,61 2,83 3,3 at 24V, 10A
Start-up delay
typ. 700ms 800ms 850ms see Fig. 5-2
Rise time typ. 35ms 35ms 35ms 0mF, 24V, 10A, see Fig. 5-2
typ. 75ms 75ms 75ms 10mF, 24V, 10A, see Fig. 5-2
Turn-on overshoot
max. 100mV 100mV 100mV see Fig. 5-2
Turn-on voltage typ. 80Vac 80Vac N / A steady-state value, see Fig. 5-1
Shut-down voltage typ. 75Vac 75Vac N / A steady-state value, see Fig. 5-1
*) The power factor is the ratio of the true (or real) power to the apparent power in an AC circuit.
**) The crest factor is the mathematical ratio of the peak value to the RMS value of the input current waveform
Fig. 5-1 Input voltage range Fig. 5-2 Turn-on behavior, definitions
Turn-on
90V
Rated input ranges
V
IN
P
OUT
264Vac180V
Shut-down
132V
no
harm
from
132 to
180V
Range
100-
120V
Range
200-
240V
Start-up
delay
Rise
Time
Overshoot
- 5%
Output
Voltage
Intput
Voltage
Fig. 5-3 Input current vs. output load Fig. 5-4 Power Factor vs. output load
12A
2
34567
8
9
0
1
2
3
4
5
6A
Input
Current, typ.
10 11
Output Current
2
3
0
V
a
c
1
2
0
V
a
c
1
0
0
V
a
c
12A
2
34 6
8
0.35
0.4
10
Output Current
5
7
9
11
0.45
0.5
0.55
0.6
0.65
Power Factor, typ.
2
3
0
V
a
c
1
2
0
V
a
c
1
0
0
V
a
c