Datasheet
CS10.241, CS10.241-S1
C-Line
24V, 10A, SINGLE PHASE INPUT
7. HOLD-UP TIME
AC 100V AC 120V AC 230V
Hold-up Time typ. 62ms 107ms 103ms at 24V, 5A, see Fig. 7-1
min. 50ms 86ms 83ms at 24V, 5A, see Fig. 7-1
typ. 23ms 46ms 47ms at 24V, 10A, see Fig. 7-1
min. 19ms 37ms 38ms at 24V, 10A, see Fig. 7-1
typ. 17ms 35ms 37ms at 24V, 12A, see Fig. 7-1
min. 14ms 28ms 30ms at 24V, 12A, see Fig. 7-1
Fig. 7-1 Hold-up time vs. input voltage Fig. 7-2 Shut-down behavior, definitions
0
20
40
120ms
85 120100 180 230Vac
Hold-up Time
80
60
100
Input Voltage
a) 24V 5A typ.
b) 24V 5A min.
c) 24V 10A typ.
d) 24V 10A min.
e) 24V 12A min.
a a
b
c
c
d
d
e
e
b
- 5%
Hold-up Time
Zero Transition
Output
Voltage
Input
Voltage
Note: At no load, the hold-up time can be up to several seconds. The green DC-OK lamp is on during this time.
Jul. 2015 / Rev. 2.0 DS-CS10.241-EN
All parameters are specified at 24V, 10A, 230Vac, 50Hz, 25°C ambient and after a 5 minutes run-in time unless otherwise noted.