Datasheet
CPS20.481-D1
C-Series
48V, 10A, DC/DC CONVERTER
22.7. SERIES OPERATION
DC/DC converters of the same type can be connected in series for higher
output voltages. It is possible to connect as many units in series as needed,
providing the sum of the output voltage does not exceed 150Vdc. Voltages
with a potential above 60Vdc are not SELV any more and can be dangerous.
Such voltages must be installed with a protection against touching.
23/25
Earthing of the output is required when the sum of the output voltage is
above 60Vdc.
Avoid return voltage (e.g. from a decelerating motor or battery) which is
applied to the output terminals.
Keep an installation clearance of 15mm (left / right) between two DC/DC
converters and avoid installing the DC/DC converters on top of each other. Do not use DC/DC converters in series in
mounting orientations other than the standard mounting orientation (terminals on bottom of the unit).
Unit A
Input
Output
Unit B
-
+
-
+
Load
+
-
Earth
(see notes)
Input
Output
Pay attention that EMI and inrush current will increase when using multiple DC/DC converters.
22.8. INDUCTIVE AND CAPACITIVE LOADS
The unit is designed to supply any kind of loads, including capacitive and inductive loads. If extreme large capacitors,
such as EDLCs (electric double layer capacitors or “UltraCaps”) with a capacitance > 0.15F are connected to the output,
the unit might charge the capacitor in the Hiccup
PLUS
mode (see chapter 6).
Oct. 2013 / Rev. 1.2 DS-CPS20.481-D1-EN
All parameters are specified at 48V, 10A, 300Vdc, 25°C ambient and after a 5 minutes run-in time unless otherwise noted.
www.pulspower.com Phone +49 89 9278 0 Germany