Datasheet
CPS20.241, CPS20.241-A1
C-Series
24V, 20A, SINGLE PHASE INPUT
4. DC-INPUT
Do not operate this power supply with DC-input voltage. Use the CPS20.241-D1 unit instead.
5. INPUT INRUSH CURRENT
An active inrush limitation circuit limits the input inrush current after turn-on of the input voltage and after short
input voltage interruptions.
The charging current into EMI suppression capacitors is disregarded in the first microseconds after switch-on.
AC 100V AC 120V AC 230V
Inrush current max. 13A
peak
*) 13A
peak
*) 13A
peak
*)
typ. 11A
peak
*) 9A
peak
*) 7A
peak
*)
Inrush energy max. 2A
2
s *) 2.5A
2
s *) 0.5A
2
s *)
Inrush delay (A) typ. 800ms 800ms 700ms see (A) in Fig. 5-1
*) Over entire temperature range; mains interruptions > 500ms
Fig. 5-1 Input inrush current, typical behavior
Input Current
Input Voltage
A
Output Voltage
A…. Inrush delay
Input: 230Vac
Output: 24V, 20A
Ambient: 25°C
Upper curve: Input current 5A / DIV
Middle curve: Input voltage 500V / DIV
Lower curve: Output voltage 20V / DIV
Time basis: 100ms / DIV
May 2012 / Rev. 1.0 DS-CPS20.241-EN
All parameters are specified at 24V, 20A, 230Vac, 25°C ambient and after a 5 minutes run-in time unless otherwise noted.
www.pulspower.com Phone +49 89 9278 0 Germany
5/25