24V, 20A, SINGLE PHASE INPUT
4. DC-INPUT
Do not operate this power supply with DC-input voltage. Use the CPS20.241-D1 unit instead.
5. INPUT INRUSH CURRENT
An active inrush limitation circuit limits the input inrush current after turn-on of the input voltage and after short
input voltage interruptions.
The charging current into EMI suppression capacitors is disregarded in the first microseconds after switch-on.
AC 100V AC 120V AC 230V
Inrush current
*)
max. 13A
peak
13A
peak
13A
peak
temperature independent
typ. 11A
peak
9A
peak
7A
peak
temperature independent
Inrush energy
*)
max. 2A
2
s 2.5A
2
s 0.5A
2
s temperature independent
Inrush delay typ. 935ms 935ms 735ms start-up delay plus rise time
*) Mains interruptions > 500ms
Fig. 5-1 Typical input inrush current
behaviour at nominal load and 25°C ambient
100mS/DIV
Output
Input
230Vac
24Vdc
Input Current 5A / DIV
Apr. 2014 / Rev. 1.6 DS-CPS20.241-EN
All parameters are specified at 24V, 20A, 230Vac, 25°C ambient and after a 5 minutes run-in time unless otherwise noted.