Datasheet

CP5.241, CP5.241-C1, CP5.241-S1,
CP5.241-S2, CP5.242
CP-Series
24V, 5A, 120W, SINGLE PHASE INPUT
Feb. 2018 / Rev. 0.3 DS-CP5.241-EN All parameters are typical values specified at 230Vac, 50Hz input voltage, 24V, 5A output load,
25°C ambient and after a 5 minutes run-in time unless otherwise noted.
www.pulspower.com Phone +49 89 9278 0 Germany
15/28
P R E L I M I N A R Y
15. EMC
The EMC behavior of the device is designed for applications in industrial environment as well as in residential,
commercial and light industry environments.
EMC Immunity
According to the generic standards EN 61000-6-1 and EN 61000-6-2.
Electrostatic discharge EN 61000-4-2 Contact discharge
Air discharge
8kV
15kV
Criterion A
Criterion A
Electromagnetic RF field EN 61000-4-3 80MHz-2.7GHz 20V/m Criterion A
Fast transients (Burst) EN 61000-4-4 Input lines
Output lines
DC-OK signal (coupling clamp)
4kV
2kV
2kV
Criterion A
Criterion A
Criterion A
Surge voltage on input EN 61000-4-5 L Æ N
L Æ PE, N Æ PE
2kV
4kV
Criterion A
Criterion A
Surge voltage on output EN 61000-4-5 + Æ -
+ / - Æ PE
1kV
2kV
Criterion A
Criterion A
Surge voltage on DC-OK EN 61000-4-5 DC-OK signal Æ PE 1kV Criterion A
Conducted disturbance EN 61000-4-6 0.15-80MHz 20V Criterion A
Mains voltage dips EN 61000-4-11 0% of 100Vac
40% of 100Vac
70% of 100Vac
0% of 200Vac
40% of 200Vac
70% of 200Vac
0Vac, 20ms
40Vac, 200ms
70Vac, 500ms
0Vac, 20ms
80Vac, 200ms
140Vac, 500ms
Criterion A
Criterion C
Criterion A
Criterion A
Criterion A <4A
Criterion C >4A
Criterion A
Voltage interruptions EN 61000-4-11 0% of 200Vac (=0V) 5000ms Criterion C
Voltage sags SEMI F47 0706 Dips on the input voltage according to SEMI F47 standard
80% of 120Vac (96Vac)
70% of 120Vac (84Vac)
50% of 120Vac (60Vac)
1000ms
500ms
200ms
Criterion A
Criterion A
Criterion A
Powerful transients VDE 0160 Over entire load range 750V, 0.3ms Criterion A
Performance criterions:
A: Power supply shows normal operation behavior within the defined limits.
C: Temporary loss of function is possible. Device may shut-down and restarts by itself. No damage or hazards for the power supply will occur.
EMC Emission
According to the generic standards EN 61000-6-3 and EN 61000-6-4.
Conducted emission
input lines
EN 55011, EN 55022, FCC Part 15, CISPR 11, CISPR 22 Class B
Conducted emission
output lines
**)
IEC/CISPR 16-1-2, IEC/CISPR 16-2-1 Class A for information only, not
mandatory for EN 61000-6-3
Radiated emission EN 55011, EN 55022 Class B
Harmonic input current (PFC) EN 61000-3-2 Class A equipment: fulfilled
Voltage fluctuations, flicker EN 61000-3-3 Fulfilled
,
tested with constant
current loads, non pulsing
This device complies with FCC Part 15 rules.
Operation is subjected to following two conditions: (1) this device may not cause harmful interference, and (2) this
device must accept any interference received, including interference that may cause undesired operation.
Switching Frequencies
PFC converter 70kHz to 130kHz Input voltage and output load dependent
Main converter 60kHz to 140kHz Output load dependent
Auxiliary converter 60kHz Fixed frequency