Datasheet

CP5.241, CP5.241-C1, CP5.241-S1,
CP5.241-S2, CP5.242
CP-Series
24V, 5A, 120W, SINGLE PHASE INPUT
Feb. 2018 / Rev. 0.3 DS-CP5.241-EN All parameters are typical values specified at 230Vac, 50Hz input voltage, 24V, 5A output load,
25°C ambient and after a 5 minutes run-in time unless otherwise noted.
www.pulspower.com Phone +49 89 9278 0 Germany
P R E L I M I N A R Y
CP5.241-S2 Input Output DC-OK-Signal
Type Push-in termination Push-in termination Push-in termination
Solid wire Max. 2.5mm
2
Max. 2.5mm
2
Max. 1.5mm
2
Stranded wire Max. 2.5mm
2
Max. 2.5mm
2
Max. 1.5mm
2
Stranded wire with ferrules Max. 1.5mm
2
Max. 1.5mm
2
Max. 1.5mm
2
American Wire Gauge AWG 24-12 AWG 24-12 AWG 24-16
Max. wire diameter (including ferrules) 2.3mm 2.3mm 1.6mm
Wire stripping length 10mm / 0.4inch 10mm / 0.4inch 7mm / 0.28inch
Screwdriver 3.0mm slotted to open
the spring
3.0mm slotted to open
the spring
3mm slotted to open
the spring
Instructions for wiring:
a) Use appropriate copper cables that are designed for minimum operating temperatures of:
60°C for ambient up to 45°C and
75°C for ambient up to 60°C and
90°C for ambient up to 70°C minimum.
b) Follow national installation codes and installation regulations!
c) Ensure that all strands of a stranded wire enter the terminal connection!
d) Unused terminal compartments should be securely tightened.
e) Ferrules are allowed.
Daisy chaining:
Daisy chaining (jumping from one power supply output to the next) is allowed as long as the average output current
through one terminal pin does not exceed 25A or 15A for the CP5.241-S2. If the current is higher, use a separate
distribution terminal block as shown in Fig. 13-2.
Fig. 13-1 Daisy chaining of outputs Fig. 13-2 Using distribution terminals
Load
+
-
Power
Supply
+ +
- -
Output
Power
Supply
+ +
- -
Output
Maximal 15A continuous for CP5.241-S2
Maximal 25A continuous for all other units
Distribution
Terminals
Load
+
-
Power
Supply
+ +
- -
Output
Power
Supply
+ +
- -
Output
13/28