Data Sheet
CP5.241, CP5.241-C1, CP5.241-S1,
CP5.241-S2, CP5.242
CP-Series
24V, 5A, 120W, SINGLE PHASE INPUT
Sep. 2018 / Rev. 0.4 DS-CP5.241-EN All parameters are typical values specified at 230Vac, 50Hz input voltage, 24V, 5A output load,
25°C ambient and after a 5 minutes run-in time unless otherwise noted.
www.pulspower.com Phone +49 89 9278 0 Germany
PRELIMINARY
12. CONNECTION TERMINALS
The terminals are IP20 Finger safe constructed and suitable for field- and factory wiring.
CP5.241, CP5.241-C1, CP5.242 Input Output DC-OK-Signal
Type Screw termination Screw termination Push-in termination
Solid wire Max. 6mm
2
Max. 6mm
2
Max. 1.5mm
2
Stranded wire Max. 4mm
2
Max. 4mm
2
Max. 1.5mm
2
American Wire Gauge AWG 20-10 AWG 20-10 AWG 24-16
Max. wire diameter (including ferrules) 2.8mm 2.8mm 1.6mm
Recommended tightening torque Max. 1Nm, 9lb-in Max. 1Nm, 9lb-in -
Wire stripping length 7mm / 0.28inch 7mm / 0.28inch 7mm / 0.28inch
Screwdriver 3.5mm slotted or cross-
head No 2
3.5mm slotted or cross-
head No 2
3mm slotted to open
the spring
CP5.241-S1 Input Output DC-OK-Signal
Type Quick-connect spring-
clamp termination
Quick-connect spring-
clamp termination
Push-in termination
Solid wire Max. 6mm
2
Max. 6mm
2
Max. 1.5mm
2
Stranded wire Max. 4mm
2
Max. 4mm
2
Max. 1.5mm
2
American Wire Gauge AWG 20-10 AWG 20-10 AWG 24-16
Max. wire diameter (including ferrules) 2.8mm 2.8mm 1.6mm
Wire stripping length 10mm / 0.4inch 10mm / 0.4inch 7mm / 0.28inch
Screwdriver - - 3mm slotted to open
the spring
CP5.241-S2 Input Output DC-OK-Signal
Type Push-in termination Push-in termination Push-in termination
Solid wire Max. 2.5mm
2
Max. 2.5mm
2
Max. 1.5mm
2
Stranded wire Max. 2.5mm
2
Max. 2.5mm
2
Max. 1.5mm
2
Stranded wire with ferrules Max. 1.5mm
2
Max. 1.5mm
2
Max. 1.5mm
2
American Wire Gauge AWG 24-12 AWG 24-12 AWG 24-16
Max. wire diameter (including ferrules) 2.3mm 2.3mm 1.6mm
Wire stripping length 10mm / 0.4inch 10mm / 0.4inch 7mm / 0.28inch
Screwdriver 3.0mm slotted to open
the spring
3.0mm slotted to open
the spring
3mm slotted to open
the spring
Daisy chaining:
Daisy chaining (jumping from one power supply output to the next) is allowed as long as the average output current
through one terminal pin does not exceed 25A or 15A for the CP5.241-S2. If the current is higher, use a separate
distribution terminal block as shown in Fig. 12-2.
Fig. 12-1 Daisy chaining of outputs Fig. 12-2 Using distribution terminals
Load
+
-
Power
Supply
+ +
- -
Output
Power
Supply
+ +
- -
Output
Maximal 15A continuous for CP5.241-S2
Maximal 25A continuous for all other units
Distribution
Terminals
Load
+
-
Power
Supply
+ +
- -
Output
Power
Supply
+ +
- -
Output
13/29