Data Sheet

CP5.241, CP5.241-C1, CP5.241-S1,
CP5.241-S2, CP5.242
CP-Series
24V, 5A, 120W, SINGLE PHASE INPUT
Sep. 2018 / Rev. 0.4 DS-CP5.241-EN All parameters are typical values specified at 230Vac, 50Hz input voltage, 24V, 5A output load,
25°C ambient and after a 5 minutes run-in time unless otherwise noted.
www.pulspower.com Phone +49 89 9278 0 Germany
PRELIMINARY
7. HOLD-UP TIME
The hold-up time is the time during which a power supply’s output voltage remains within specification following the
loss of input power. The hold-up time is output load dependent. At no load, the hold-up time can be up to several
seconds. The green DC-ok lamp is also on during this time.
AC 100V AC 120V AC 230V
Hold-up Time Typ. 70ms 70ms 70ms At 24V, 2.5A, see Fig. 7-1
Min. 55ms 55ms 55ms At 24V, 2.5A, see Fig. 7-1
Typ. 35ms 35ms 35ms At 24V, 5A, see Fig. 7-1
Min. 27ms 27ms 27ms At 24V, 5A, see Fig. 7-1
Fig. 7-1 Hold-up time vs. input voltage Fig. 7-2 Shut-down behavior, definitions
10/29
0
15
30
45
60
90ms
90 120 155 190 230Vac
Input Voltage
75
Hold-up Time
a
b
c
d
a) 24V 2.5A typ.
b) 24V 2.5A min.
c) 24V 5A typ.
d) 24V 5A min.
- 5%
Zero Transition
Output
Input
Voltage
Hold-up Time
Voltage
8. DC-OK RELAY CONTACT
This feature monitors the output voltage on the output terminals of a running power supply.
Contact closes As soon as the output voltage reaches typ. 90% of the adjusted output voltage level.
Contact opens As soon as the output voltage dips more than 10% below the adjusted output voltage.
Short dips will be extended to a signal length of 100ms. Dips shorter than 1ms will be ignored.
Switching hysteresis Typically 0.7V
Contact ratings Maximal 60Vdc 0.3A, 30Vdc 1A, 30Vac 0.5A, resistive load
Minimal permissible load: 1mA at 5Vdc
Isolation voltage See dielectric strength table in section 18.
Fig. 8-1 DC-ok relay contact behavior
V
OUT
= V
ADJ
100ms
0.9* V
ADJ
<
1ms
10%
>
1...4ms
open openclosed closed