Datasheet
CP5.241, CP5.241-C1, CP5.241-S1,
CP5.241-S2, CP5.242
CP-Series
24V, 5A, 120W, SINGLE PHASE INPUT
Sep. 2018 / Rev. 0.4 DS-CP5.241-EN All parameters are typical values specified at 230Vac, 50Hz input voltage, 24V, 5A output load,
25°C ambient and after a 5 minutes run-in time unless otherwise noted.
www.pulspower.com Phone +49 89 9278 0 Germany
PRELIMINARY
4. DC-INPUT
The device is suitable to be supplied from a DC input voltage. Use a battery or a similar DC source. A supply from the
intermediate DC-bus of a frequency converter is not recommended and can cause a malfunction or damage the unit.
Connect +pole to L, –pole to N and the PE terminal to an earth wire or to the machine ground.
DC input Nom. DC 110-150V ±20%
For CP5.241, CP5.241-C1, CP5.241-S1, CP5.241-S2
Nom. DC 110-300V ±20%
For CP5.242
DC input range Min. 88-180Vdc Continuous operation
For CP5.241, CP5.241-C1, CP5.241-S1, CP5.241-S2
88-360Vdc Continuous operation for CP5.242
DC input current Typ. 1.21A At 110Vdc, at 24V, 5A
Typ. 0.43A At 300Vdc, at 24V, 5A
Allowed Voltage (+) or (-) input
to Earth
Max. 360Vdc Continuous according to IEC 60664-1
Turn-on voltage Typ. 74Vdc Steady state value
Shut-down voltage Typ. 67Vdc Steady state value
Fig. 4-1 Wiring for DC Input
6/29
+
-
Load
L
PE
+
-
Power Supply
AC
DC
Battery
N