Datasheet

CP5.241, CP5.241-C1, CP5.241-S1,
CP5.241-S2, CP5.242
CP-Series
24V, 5A, 120W, SINGLE PHASE INPUT
Sep. 2018 / Rev. 0.4 DS-CP5.241-EN All parameters are typical values specified at 230Vac, 50Hz input voltage, 24V, 5A output load,
25°C ambient and after a 5 minutes run-in time unless otherwise noted.
www.pulspower.com Phone +49 89 9278 0 Germany
PRELIMINARY
23.6. OPERATION ON TWO PHASES
240V
+10%
max.
L2
L1
L3
L
N
PE
Power Supply
AC
DC
The power supply can also be used on two-phases of a three-phase-system.
Such a phase-to-phase connection is allowed as long as the supplying
voltage is below 240V
+10%
.
Ensure that the wire, which is connected to the N-terminal, is
appropriately fused.
The maximum allowed voltage between a Phase and the PE must be
below 300Vac.
23.7. USE IN A TIGHTLY SEALED ENCLOSURE
When the power supply is installed in a tightly sealed enclosure, the temperature inside the enclosure will be higher
than outside. In such situations, the inside temperature defines the ambient temperature for the power supply.
The following measurement results can be used as a reference to estimate the temperature rise inside the enclosure.
The power supply is placed in the middle of the box, no other heat producing items are inside the box
The temperature sensor inside the box is placed in the middle of the right side of the power supply with a distance of
1cm.
The following measurement results can be used as a reference to estimate the temperature rise inside the enclosure.
Case A Case B
Enclosure size 110x180x165mm
Rittal Typ IP66 Box
PK 9516 100,
plastic
110x180x165mm
Rittal Typ IP66 Box
PK 9516 100,
plastic
Input voltage 230Vac 230Vac
Load
24V, 4A; (=80%) 24V, 5A; (=100%)
Temperature inside the box 38.3°C 39.6°C
Temperature outside the box 26.1°C 25.5°C
Temperature rise 12.2K 14.1K
28/29