Cut Sheet
Table Of Contents
- 1. Intended Use
- 2. Installation Instructions
- 3. AC-Input
- 4. DC-Input
- 5. Input Inrush Current
- 6. Output
- 7. Hold-up Time
- 8. DC-OK Relay Contact
- 9. Efficiency and Power Losses
- 10. Functional Diagram
- 11. Front Side and User Elements
- 12. Connection Terminals
- 13. Lifetime Expectancy
- 14. MTBF
- 15. EMC
- 16. Environment
- 17. Safety and Protection Features
- 18. Dielectric Strength
- 19. Approved, Fulfilled or Tested Standards
- 20. Regulatory Product Compliance
- 21. Physical Dimensions and Weight
- 22. Accessories
- 22.1. ZM10.WALL - Wall/Panel Mount Bracket
- 22.2. YR20.242 - Redundancy Module
- 23. Application Notes
- 23.1. Peak Current Capability
- 23.2. Charging of Batteries
- 23.3. Series Operation
- 23.4. Parallel Use to Increase Output Power
- 23.5. Parallel Use for Redundancy
- 23.6. Operation on Two Phases
- 23.7. Use in a Tightly Sealed Enclosure
- 23.8. Mounting Orientations
CP5.121
CP
-Series
12V, 10A, 120W, SINGLE PHASE INPUT
Aug 2021 / Rev. 1.2 DS-CP5.121-EN All values are typical figures specified at 230Vac, 50Hz input voltage, 12V 10A output load,
25°C ambient and after a 5 minutes run-in time unless otherwise noted.
www.pulspower.com Phone +49 89 9278 0 Germany
5/28
3. AC-I
NPUT
The device is suitable to be supplied from TN, TT or IT mains networks with AC voltage. For suitable DC supply voltages
see chapter 4.
AC input
Nom. AC 100-240V
AC inpu
t range 85-264Vac Continuous operation
264-300Vac Occasionally for maximal 500ms
Allowed voltage L or N to earth
Max. 300Vac Continuous, according to IEC 606641
Input frequency
Nom. 50–60Hz ±6%
Turn
-on voltage Typ. 80Vac Steady-state value, see Fig. 3-1
Shut
-down voltage Typ. 74Vac Steady-state value, see Fig. 3-1
External input protection
See recommendations in chapter 2.
AC 100V AC 120V AC 230V
Input current
Typ. 1.30A 1.09A 0.60A At 12V, 10A, see Fig. 3-3
Power factor
Typ. 0.99 0.98 0.91 At 12V, 10A, see Fig. 3-4
Cre
st factor Typ. 1.7 1.8 2.2
At 12V, 10A The crest factor is the
mathematical ratio of the peak
value to RMS value of the input
current waveform.
Start
-up delay Typ. 400ms 350ms 375ms See Fig. 3-2
Rise time
Typ. 30ms 30ms 30ms
At 12V, 10A const. current load,
0mF load capacitance, see Fig. 3-2
Typ. 50ms 50ms 50ms
At 12V, 10A const. current load,
10mF load capacitance,, see Fig. 3-2
Turn
-on overshoot Max. 200mV 200mV 200mV See Fig. 3-2
Fig. 3-1 Input voltage range Fig. 3-2 Turn-on behavior, definitions
Turn-on
85V
Rated
input range
max.
500ms
V
IN
P
OUT
300Vac264V
Shut-down
Start-up
delay
Rise
Time
Overshoot
- 5%
Output
Voltage
Input
Voltage