Cut Sheet
Table Of Contents
- 1. Intended Use
- 2. Installation Instructions
- 3. AC-Input
- 4. DC-Input
- 5. Input Inrush Current
- 6. Output
- 7. Hold-up Time
- 8. DC-OK Relay Contact
- 9. Efficiency and Power Losses
- 10. Functional Diagram
- 11. Front Side and User Elements
- 12. Connection Terminals
- 13. Lifetime Expectancy
- 14. MTBF
- 15. EMC
- 16. Environment
- 17. Safety and Protection Features
- 18. Dielectric Strength
- 19. Approved, Fulfilled or Tested Standards
- 20. Regulatory Product Compliance
- 21. Physical Dimensions and Weight
- 22. Accessories
- 22.1. ZM10.WALL - Wall/Panel Mount Bracket
- 22.2. YR20.242 - Redundancy Module
- 23. Application Notes
- 23.1. Peak Current Capability
- 23.2. Charging of Batteries
- 23.3. Series Operation
- 23.4. Parallel Use to Increase Output Power
- 23.5. Parallel Use for Redundancy
- 23.6. Operation on Two Phases
- 23.7. Use in a Tightly Sealed Enclosure
- 23.8. Mounting Orientations
CP5.121
CP
-Series
12V, 10A, 120W, SINGLE PHASE INPUT
Aug 2021 / Rev. 1.2 DS-CP5.121-EN All values are typical figures specified at 230Vac, 50Hz input voltage, 12V 10A output load,
25°C ambient and after a 5 minutes run-in time unless otherwise noted.
www.pulspower.com Phone +49 89 9278 0 Germany
4/28
Keep the following minimum installation clearances: 40mm on top, 20mm on the bottom, 5mm left and right side.
Increase the 5mm to 15mm in case the adjacent device is a heat source. When the device is permanently loaded with
less than 50%, the 5mm can be reduced to zero.
The device is designed, tested and approved for branch circuits up to 32A (IEC) and 30A (UL) without additional
protection device. If an external fuse is utilized, do not use circuit breakers smaller than 6A B- or C-Characteristic to
avoid a nuisance tripping of the circuit breaker.
The maximum surrounding air temperature is +70°C (+158°F). The operational temperature is the same as the ambient
or surrounding air temperature and is defined 2cm below the device.
The device is designed to operate in areas between 5% and 95% relative humidity.
Installation Instructions for Hazardous Location Areas
The device is suitable for use in Class I Division 2 Groups A, B, C, D locations and for use in Group II Category 3 (Zone 2)
environments.
Classification: ATEX: EPS 19 ATEX 1 201 X, II 3G EX ec nC IIC T4 Gc / IECEx EPS 19.0078X
WARNING EXPLOSION HAZARDS!
Use only in standard vertical mounting orientation with the input terminals on bottom of the unit. Substitution of
components may impair suitability for this environment.
Do not disconnect the device or operate the voltage adjustment unless power has been switched off or the area is
known to be non-hazardous.
A suitable enclosure must be provided for the end product which has a minimum protection of IP54 and fulfils the
requirements of the EN 60079-0.