Cut Sheet
Table Of Contents
- 1. Intended Use
- 2. Installation Instructions
- 3. AC-Input
- 4. DC-Input
- 5. Input Inrush Current
- 6. Output
- 7. Hold-up Time
- 8. DC-OK Relay Contact
- 9. Efficiency and Power Losses
- 10. Functional Diagram
- 11. Front Side and User Elements
- 12. Connection Terminals
- 13. Lifetime Expectancy
- 14. MTBF
- 15. EMC
- 16. Environment
- 17. Safety and Protection Features
- 18. Dielectric Strength
- 19. Approved, Fulfilled or Tested Standards
- 20. Regulatory Product Compliance
- 21. Physical Dimensions and Weight
- 22. Accessories
- 22.1. ZM10.WALL - Wall/Panel Mount Bracket
- 22.2. YR20.242 - Redundancy Module
- 23. Application Notes
- 23.1. Peak Current Capability
- 23.2. Charging of Batteries
- 23.3. Series Operation
- 23.4. Parallel Use to Increase Output Power
- 23.5. Parallel Use for Redundancy
- 23.6. Operation on Two Phases
- 23.7. Use in a Tightly Sealed Enclosure
- 23.8. Mounting Orientations
CP5.121
CP
-Series
12V, 10A, 120W, SINGLE PHASE INPUT
Aug 2021 / Rev. 1.2 DS-CP5.121-EN All values are typical figures specified at 230Vac, 50Hz input voltage, 12V 10A output load,
25°C ambient and after a 5 minutes run-in time unless otherwise noted.
www.pulspower.com Phone +49 89 9278 0 Germany
28/28
23.8. MOUNTING ORIENTATIONS
Mounting orientations other than input terminals on the bottom and output on the top require a reduction in
continuous output power or a limitation in the maximum allowed ambient temperature.
The listed lifetime and MTBF values from this datasheet apply only for the standard mounting orientation.
The following curves give an indication for allowed output currents for altitudes up to 2000m (6560ft).
Fig. 23-6
Mounting
Orientation A
(Standard
orientation)
Power
Supply
OUTPUT
INPUT
Allowed Output Current at 12V
0
+45 +70°C
7.5A
10A
12A
Ambient Temperature
+60
Fig. 23-7
Mounting
Orientation B
(Upside down)
Power
Supply
OUTPUT
INPUT
Allowed Output Current at 12V
0
+30 +70°C
7.5A
12A
Ambient Temperature
+60
Fig. 23-8
Mounting
Orientation C
(Table-top
mounting)
Allowed Output Current at 12V
0
+25 +70°C
6.5A
12A
Ambient Temperature
+60
Fig. 23-9
Mounting
Orientation D
(Horizontal cw)
Power
Supply
OUTPUT
INPUT
Allowed Output Current at 12V
0
+25 +70°C
6.5A
12A
Ambient Temperature
+60
Fig. 23-10
Mounting
Orientation E
(Horizontal ccw)
Power
Supply
OUTPUT
INPUT
Allowed Output Current at 12V
0
+25
+70°C
6.5A
12A
Ambient Temperature
+60