Cut Sheet
Table Of Contents
- 1. Intended Use
- 2. Installation Instructions
- 3. AC-Input
- 4. DC-Input
- 5. Input Inrush Current
- 6. Output
- 7. Hold-up Time
- 8. DC-OK Relay Contact
- 9. Efficiency and Power Losses
- 10. Functional Diagram
- 11. Front Side and User Elements
- 12. Connection Terminals
- 13. Lifetime Expectancy
- 14. MTBF
- 15. EMC
- 16. Environment
- 17. Safety and Protection Features
- 18. Dielectric Strength
- 19. Approved, Fulfilled or Tested Standards
- 20. Regulatory Product Compliance
- 21. Physical Dimensions and Weight
- 22. Accessories
- 22.1. ZM10.WALL - Wall/Panel Mount Bracket
- 22.2. YR20.242 - Redundancy Module
- 23. Application Notes
- 23.1. Peak Current Capability
- 23.2. Charging of Batteries
- 23.3. Series Operation
- 23.4. Parallel Use to Increase Output Power
- 23.5. Parallel Use for Redundancy
- 23.6. Operation on Two Phases
- 23.7. Use in a Tightly Sealed Enclosure
- 23.8. Mounting Orientations
CP5.121
CP
-Series
12V, 10A, 120W, SINGLE PHASE INPUT
Aug 2021 / Rev. 1.2 DS-CP5.121-EN All values are typical figures specified at 230Vac, 50Hz input voltage, 12V 10A output load,
25°C ambient and after a 5 minutes run-in time unless otherwise noted.
www.pulspower.com Phone +49 89 9278 0 Germany
27/28
23.6. OPERATION ON TWO PHASES
The power supply can also be used on two-phases of a three-phase-
system. Such a phase-to-phase connection is allowed as long as the
supplying voltage is below 240V
+10%
.
Ensure that the wire, which is connected to the N-terminal, is
appropriately fused.
The maximum allowed voltage between a Phase and the PE must be
below 300Vac.
23.7. USE IN A TIGHTLY SEALED ENCLOSURE
When the device is installed in a tightly sealed enclosure, the temperature inside the enclosure will be higher than
outside. In such situations, the inside temperature defines the ambient temperature for the device.
In the following test setup, the device is placed in the middle of the box, no other heat producing items are inside the
box. The load is placed outside the box.
The temperature sensor inside the box is placed in the middle of the right side of the power supply with a distance of
1cm.
The following measurement results can be used as a reference to estimate the temperature rise inside the enclosure.
Case A Case B
Enclosure size
110x180x165mm
Rittal Typ IP66 Box
PK 9516 100,
plastic
110x180x165mm
Rittal Typ IP66 Box
PK 9516 100,
plastic
Input voltage
230Vac 230Vac
Load
12V, 8A; (=80%) 12V, 10A; (=100%)
Temperature inside the box
40.7°C
43.2°C
Temperature outside the box
27.9°C
28.0°C
Temperature rise
12.8K
15.2K