Cut Sheet
Table Of Contents
- 1. Intended Use
- 2. Installation Instructions
- 3. AC-Input
- 4. DC-Input
- 5. Input Inrush Current
- 6. Output
- 7. Hold-up Time
- 8. DC-OK Relay Contact
- 9. Efficiency and Power Losses
- 10. Functional Diagram
- 11. Front Side and User Elements
- 12. Connection Terminals
- 13. Lifetime Expectancy
- 14. MTBF
- 15. EMC
- 16. Environment
- 17. Safety and Protection Features
- 18. Dielectric Strength
- 19. Approved, Fulfilled or Tested Standards
- 20. Regulatory Product Compliance
- 21. Physical Dimensions and Weight
- 22. Accessories
- 22.1. ZM10.WALL - Wall/Panel Mount Bracket
- 22.2. YR20.242 - Redundancy Module
- 23. Application Notes
- 23.1. Peak Current Capability
- 23.2. Charging of Batteries
- 23.3. Series Operation
- 23.4. Parallel Use to Increase Output Power
- 23.5. Parallel Use for Redundancy
- 23.6. Operation on Two Phases
- 23.7. Use in a Tightly Sealed Enclosure
- 23.8. Mounting Orientations
CP5.121
CP
-Series
12V, 10A, 120W, SINGLE PHASE INPUT
Aug 2021 / Rev. 1.2 DS-CP5.121-EN All values are typical figures specified at 230Vac, 50Hz input voltage, 12V 10A output load,
25°C ambient and after a 5 minutes run-in time unless otherwise noted.
www.pulspower.com Phone +49 89 9278 0 Germany
25/28
23.2. CHARGING OF BATTERIES
The power supply can be used to charge lead-acid or maintenance free VRLA batteries.
Instructions for charging batteries:
a) Ensure that the ambient temperature of the power supply stays below 40°C.
b) Use a 15A or 16A circuit breaker or a blocking diode between the power supply and the battery.
c) Ensure that the output current of the power supply is below the allowed charging current of the battery.
d) The return current to the power supply is typically 8mA. This return current can discharge the battery when the
power supply is switched off except in case a blocking diode is utilized.
e) Set the output voltage, measured at no load and at the battery end of the cable, very precisely to the end-of-
charge voltage. Set the output voltage, measured at no load and at the battery end of the cable, very precisely to
the end-of-charge voltage. The voltage should be set to 13.9V at 10°C, 13.75V at 20°C, 13.6V at 30°C and 13.4V at
40°C ambient temperature.
23.3. SERIES OPERATION
Devices of the same type can be connected in series for higher output voltages.
It is possible to connect as many units in series as needed, providing the sum of
the output voltage does not exceed 150Vdc. Voltages with a potential above
60Vdc must be installed with a protection against touching.
Avoid return voltage (e.g. from a decelerating motor or battery) which is
applied to the output terminals.
Keep an installation clearance of 15mm (left / right) between two power
supplies and avoid installing the power supplies on top of each other. Do not
use power supplies in series in mounting orientations other than the standard
mounting orientation.
Pay attention that leakage current, EMI, inrush current, harmonics will increase when using multiple devices.
23.4. PARALLEL USE TO INCREASE OUTPUT POWER
Devises can be paralleled to increase the output power. The output voltage
shall be adjusted to the same value (±100mV) with the same load conditions on
all devices, or the devices can be left with the factory settings.
The ambient temperature is not allowed to exceed +40°C.
If more than three devices are connected in parallel, a fuse or circuit breaker
with a rating of 15A or 16A is required on each output. Alternatively, a diode
or redundancy module can also be utilized.
Energize all devices at the same time. It also might be necessary to cycle the
input power (turn-off for at least five seconds), if the output was in overload
or short circuits and the required output current is higher than the current of
one unit.
Keep an installation clearance of 15mm (left / right) between two devices and avoid installing devices on top of each
other. Do not use devices in parallel in mounting orientations other than the standard mounting orientation or in any
other condition where a reduction of the output current is required (e.g. altitude).
Pay attention that leakage current, EMI, inrush current will increase when using multiple devices.
Unit A
Unit B
-
+
-
+
Load
+
-
Input
Output
Input
Output
Unit A
Input
Output
Unit B
-
+
-
+
Load
+
-
Input
Output










